background image

5

PRO

3

 Top Mount Packaged Refrigeration System | Outdoor

1.

 O

wner

’s 

O

per

ating

 Instr

uc

tions

Rigging 

Rigging holes are provided on all models. Caution should be 

exercised when moving these units. To prevent damage to 

the unit housing during rigging, cables or chains used must 

be held apart by spacer bars. The mounting platform or base 

should be level and located so as to permit free access of 

supply air.  The unit weather hood may be removed for the 

rigging process.  The condensing unit cover (wrapper) should 

be left in place.

Access Requirements

Provide adequate space at the compressor end of the unit for 

servicing. Provide two (2) feet of space above unit for service.

Mounting 

The system requires an opening in the ceiling to the 

dimensions stated on page 3. Mounting rails are located 

at both ends of the chassis. Mounting rails may be used to 

attach unit to ceiling. Through-bolts should be insulated or 

non-conductive to prevent sweating. The chassis is weather 

stripped around the air grille and will seal to the box roof. 

The trim ring (shipped loose), when provided, should be 

installed around the air diffuser when secured with the 

hardware provided. Be sure to adhere to your local standard 

construction codes.

Inspection

1.  Each shipment should be carefully checked against the 

bill of lading.

2.  The shipping receipt should not be signed until all items 

listed on the bill of lading have been accounted for.

3.  Check packaging for signs of damage.
4.  Any shortage or damages should be immediately 

reported to the delivering carrier.

5.  Damaged material becomes the delivering carrier’s 

responsibility, and should not be  returned to the 

manufacturer unless prior approval is given to do so.

6.  When unpacking the system, care should be taken to 

prevent damage.

7.  Avoid removing the shipping base until the unit has been 

moved to the final destination.

8.  Complete warranty return card for each unit and mail to 

Heatcraft Refrigeration Products.

General Safety Information

1.  Installation and maintenance to be performed only by 

licensed contractor.

2.  Ensure that the structural integrity of the box can 

withstand the weight of the 

 (See page 2 for unit 

weights).

3.  Avoid contact with sharp edges and coil surfaces.  

They are a potential injury hazard.  Wear gloves during 

moving and rigging.

4.  Make sure all power sources are disconnected before 

any service work is done on units.

Trim Pieces (4)
Overlap as Shown

Evaporator Grill

Self Drilling Screw

Ceiling of Walk-in.

Trim Ring 

Installation 

Detail

TABLE 4

  Control Factory Default Settings

PTT  

Models

Temperature 

Set Points

Defrost 

Start Times

Defrost Duration 

(Maximum)

Drip

Time

Fan 

Delay

Defrost Termination

Set Point

EZY 

Default

H - Cooler Models

    Air Defrost

38˚F

4 / day

60 min.

38˚F

3

M - Cooler Models

    Electric Defrost

34˚F

4 / day

40 min.

2 min.

2 min.

65˚F

2

L - Freezer Models

    Electric Defrost

-10˚F

4 / day

40 min.

2 min.

2 min.

65˚F

1

Changing the EZY 

1.  Press Set button and hold in  until the display flashes "PS".
2.  Press the Set Button and the display will change to "0" and 

will begin to flash.

3.  Press the up button until "22" is displayed.
4.   Press the Set button.
5.  Press the down button 2 times.  "EZY" will be displayed.
6.  Press the Set button.
7.  Select  the  proper  number  for  the  model  needed  by 

pressing the up or down key.

•  1 - L Low temperature model
•  2 - M Med temperature model
•  3 - H High temperature model

8.  Press Set and wait for unit to return out of programming 

mode.

9.  Disconnect power
10. Press the Set Button while turning unit On
11.  "CE" should display to verify programming display

Summary of Contents for PRO TOP MOUNT H-IM-82C

Page 1: ...nit Placement 4 Rigging Mounting Inspection General Safety Information Control Factory Default Settings 5 Standard Installation Procedure 6 Outdoor Unit Installation Instructions 7 2 Freezers Service...

Page 2: ...ox Temp lbs kg oz BTUH PTT047M6B 5 120 208 230 1 60 7 0 15 5 9 350 A 192 87 27 6 700 PTT063M6B 6 860 208 230 1 60 11 5 15 9 5 550 A 207 94 29 8 700 PTT072M6B 7 500 208 230 1 60 9 3 15 7 8 500 A 211 95...

Page 3: ...ood See reference on Page 2 Dimensional Diagrams Figure B Large Cabinet without weather hood See reference on Page 2 25 x 381 2 panel opening required for evaporator section of large cabinet sizes 23...

Page 4: ...ck any panel cam locks to install top mounted equipment The size and shape of the storage will generally determine the type and number of units to be used and their location Top View One System Evapor...

Page 5: ...prior approval is given to do so 6 When unpacking the system care should be taken to prevent damage 7 Avoid removing the shipping base until the unit has been moved to the final destination 8 Complete...

Page 6: ...nstallation to prevent bunching or folding which could affect the gasket to curb sealing or trap rainwater adjacent to the curb 4 Remove the weather hood from the system The compressor compartment cov...

Page 7: ...re 2 Roof membrane placed over curb Figure 3 PTT unit placed on roof of walk in color see rigging instructions Figure 4 Weather hood installed after electrical service connection PTT Models Example Ou...

Page 8: ...functioning properly 8 Clean the evaporator coil surface 9 Clean the drain pan and check the drain pan and drain line for proper drainage Refrigeration Sequence of Operation 1 Power is provided to the...

Page 9: ...Off Off Off If unit shows OFF depress the button and hold for three seconds On Automatic Defrost on start up Off Off Off On If coil temperature is below 65 F If it is above defrost is not initiated D...

Page 10: ...Compressor starts and evaporator fans delay for 2 minutes to freeze coil TABLE 6 Model PTT Medium Temperature Models EZY SETTING 2 SET POINT IS 34 F These models are intended for cooler applications a...

Page 11: ...lling template If necessary unscrew the two screws Do not unscrew excessively the screws must not be detached from the front panel phase 1 Insert the instrument in the opening in the panel and hold it...

Page 12: ...section of each wire 0 5 mm2 Avoid direct contact with internal electronic components Connection errors and connections other than those indicated in this manual may involve danger to the safety of th...

Page 13: ...al timer relating to parameter dI is updated If dI expires in OFF status a defrost is performed when restarting auxiliary relay management only in the following configurations H1 1 2 E0 alarm only H1...

Page 14: ...multifunction input analogue or digital Parameter 4 selects the probe shown on the display all the other display and control modes remain unchanged IMPORTANT the easy compact models can display up to...

Page 15: ...arameters with corresponding values for the control of the refrigeration system Table of Alarms and Signals When an alarm is activiated the display shows the corresponding message that flashes alterna...

Page 16: ...Ad and A0 The alarm is automatically reset when the temperature returns within the set limits see parameter AL HI flashing High temperature alarm The probe has measured a temperature higher than the s...

Page 17: ...until displaying 22 password to access the parameters press the SET button to confirm the password use the UP and DOWN buttons to scroll the parameters The LED corresponding to the category of paramet...

Page 18: ...mperature is too high parameters dt and d defrost probe the manual defrost is not activated and the defrost LED flashes compressor protection times set parameter d9 select d9 1 the high temperature al...

Page 19: ...0 r2 Maximum set point value 0 150 50 c2 Minimum compressor off time 0 100 4 do Type of Defrost 0 4 0 dI Interval between defrost 0 199 6 dt End defrost temperature set point 50 127 65 dP Maximum def...

Page 20: ...for proper superheat 4 Condensing temperature too low 4 Check ambient temperature 50 F to 100 F Compressor 1 Operating beyond design conditions 1 Add equipment so that conditions are within allowable...

Page 21: ...230V Defrost Heaters 4313F 3 3 3 3 3 3 3 3 Outdoor Parts Fan Pressure Control 28917301 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Fan Temperature Control 5521R 1 1 1 1 1 1 1 1 1 1 1 1 Drain Line Heate...

Page 22: ...PRIMARY SINGLE PHASE PROTECTION PROVIDED PRIMARY SINGLE PHASE PROTECTION PROVIDED CCH CRANKCASE HEATER PFC PRESSURE FAN CYCLE SWITCH DLT DRAIN LINE THERMOSTAT DLH DRAIN LINE HEATER TFC TEMPERATURE FA...

Page 23: ...ACITOR HPS HIGH PRESSURE SWITCH PRIMARY SINGLE PHASE PROTECTION PROVIDED PRIMARY SINGLE PHASE PROTECTION PROVIDED CCH CRANKCASE HEATER PFC PRESSURE FAN CYCLE SWITCH DLT DRAIN LINE THERMOSTAT DLH DRAIN...

Page 24: ...URE SWITCH PRIMARY SINGLE PHASE PROTECTION PROVIDED PRIMARY SINGLE PHASE PROTECTION PROVIDED CCH CRANKCASE HEATER PFC PRESSURE FAN CYCLE SWITCH DLT DRAIN LINE THERMOSTAT DLH DRAIN LINE HEATER TFC TEMP...

Page 25: ...Heatcraft Refrigeration Products LLC makes no warranty expressed or implied of fitness for any particular purpose or of any other nature whatsoever with respect to products manufactured or sold by Hea...

Page 26: ...is a continuing effort we reserve the right to make changes in specifications without notice Heatcraft Refrigeration Products LLC 2175 West Park Place Blvd Stone Mountain GA 30087 P 800 321 1881 www h...

Reviews: