background image

6

Installation and Operations Manual

1.

 O

wner's

 O

per

ating
 Instr
uc

tions

The Outdoor 

 comes standard with the 

following additional components:

 

•  Crankcase Heater

 

•  Drain Line Heater

 

•  Weather Hood

 

•  Fan Cycling

 

 

 

(Pressure on 1 fan models, Pressure and Ambient 

 

 

on 2 fan models).

Standard Installation Procedure 

PTT Models

For outdoor use 

  1.  Provide a 25" X 25" (medium cabinet) or  

 

  25" X 38.5" (large cabinet) opening in the  

 

  roof of walk-in cooler or as specified by the  

 

  panel manufacturer. 

 

  2.  Apply silicone caulk around the perimeter of roof  

 

  opening. Place the curb on roof of cooler. It is  

 

 

  recommended that the curb be fastened to  

 

  the roof panels using non-conductive bolts or  

 

  insulating the bolt  heads. Bolt heads should be  

 

  countersunk or low profile to prevent contact with  

 

  the 

 system. (See Figure 1, page 7) Check the 

 

  top of the curb with a level. 

 units require 

 

  a surface that is within 1° of level or better and no  

 

  more than a 5/8" drop per 3 feet  

 

  (17mm drop per meter). 

 

  3.  Install the membrane onto the roof of the box and  

 

  over the curb. Fasten to roof per panel  

 

  manufacturer's instructions. The membrane  

 

  material should be slit over the evaporator grill  

 

  opening the flaps allowed to drape into the hole  

 

  2" - 4". (See Figure 2, page 7) Care should be taken 

 

  during the membrane installation to prevent  

 

  bunching or folding which could affect the gasket- 

 

  to-curb sealing or trap rainwater adjacent to the  

 

  curb. 

 

  4.  Remove the weather hood from the 

 system. 

 

  The compressor compartment cover(s) should be  

 

  left in place during lifting/rigging. 

 

  5.  Place 

 system onto curbing and center over 

 

  opening in roof box. (See Figure 3, page 7) 

 

  6.  It is recommended that the 

 system be 

 

  secured to the curb with wood screws. Seal  

 

  the screw heads as necessary to prevent  

 

 

  moisture from entering beneath the membrane.  

 

  Additional caulk may be applied around the  

 

  perimeter of the evaporator box gasket. The  

 

  compressor compartment should not be caulked. 

  7.  Install trim pieces (if used) around the ceiling  
 

  opening in cooler.

 

General Safety information:

Do NOT lift the 

 by the weather hood.

This product is not designed to be transported while 

installed or operating.

  8.  Remove compressor compartment cover for 

 

  access to electrical box. 

 

  9.  Connect power wiring in accordance with all  

 

  applicable building and electrical codes.  

 

  10.  Reinstall condensing unit cover(s). 

 

  11.  Reinstall the protective weather hood.  

 

  (See Figure 4, page 7)

 

  12.  Apply power and check for proper operation.

Condensate Drain 

Outlet Location

Drain Line

A condensate drain outlet is located on the side of the 

compressor compartment.  Field piping may be connected 

to the outlet provided it is adequately sloped and heated 

for freezing weather conditions.  There is a drain line "P" trap 

located in the PTT unit.

Summary of Contents for PRO TOP MOUNT H-IM-82C

Page 1: ...nit Placement 4 Rigging Mounting Inspection General Safety Information Control Factory Default Settings 5 Standard Installation Procedure 6 Outdoor Unit Installation Instructions 7 2 Freezers Service...

Page 2: ...ox Temp lbs kg oz BTUH PTT047M6B 5 120 208 230 1 60 7 0 15 5 9 350 A 192 87 27 6 700 PTT063M6B 6 860 208 230 1 60 11 5 15 9 5 550 A 207 94 29 8 700 PTT072M6B 7 500 208 230 1 60 9 3 15 7 8 500 A 211 95...

Page 3: ...ood See reference on Page 2 Dimensional Diagrams Figure B Large Cabinet without weather hood See reference on Page 2 25 x 381 2 panel opening required for evaporator section of large cabinet sizes 23...

Page 4: ...ck any panel cam locks to install top mounted equipment The size and shape of the storage will generally determine the type and number of units to be used and their location Top View One System Evapor...

Page 5: ...prior approval is given to do so 6 When unpacking the system care should be taken to prevent damage 7 Avoid removing the shipping base until the unit has been moved to the final destination 8 Complete...

Page 6: ...nstallation to prevent bunching or folding which could affect the gasket to curb sealing or trap rainwater adjacent to the curb 4 Remove the weather hood from the system The compressor compartment cov...

Page 7: ...re 2 Roof membrane placed over curb Figure 3 PTT unit placed on roof of walk in color see rigging instructions Figure 4 Weather hood installed after electrical service connection PTT Models Example Ou...

Page 8: ...functioning properly 8 Clean the evaporator coil surface 9 Clean the drain pan and check the drain pan and drain line for proper drainage Refrigeration Sequence of Operation 1 Power is provided to the...

Page 9: ...Off Off Off If unit shows OFF depress the button and hold for three seconds On Automatic Defrost on start up Off Off Off On If coil temperature is below 65 F If it is above defrost is not initiated D...

Page 10: ...Compressor starts and evaporator fans delay for 2 minutes to freeze coil TABLE 6 Model PTT Medium Temperature Models EZY SETTING 2 SET POINT IS 34 F These models are intended for cooler applications a...

Page 11: ...lling template If necessary unscrew the two screws Do not unscrew excessively the screws must not be detached from the front panel phase 1 Insert the instrument in the opening in the panel and hold it...

Page 12: ...section of each wire 0 5 mm2 Avoid direct contact with internal electronic components Connection errors and connections other than those indicated in this manual may involve danger to the safety of th...

Page 13: ...al timer relating to parameter dI is updated If dI expires in OFF status a defrost is performed when restarting auxiliary relay management only in the following configurations H1 1 2 E0 alarm only H1...

Page 14: ...multifunction input analogue or digital Parameter 4 selects the probe shown on the display all the other display and control modes remain unchanged IMPORTANT the easy compact models can display up to...

Page 15: ...arameters with corresponding values for the control of the refrigeration system Table of Alarms and Signals When an alarm is activiated the display shows the corresponding message that flashes alterna...

Page 16: ...Ad and A0 The alarm is automatically reset when the temperature returns within the set limits see parameter AL HI flashing High temperature alarm The probe has measured a temperature higher than the s...

Page 17: ...until displaying 22 password to access the parameters press the SET button to confirm the password use the UP and DOWN buttons to scroll the parameters The LED corresponding to the category of paramet...

Page 18: ...mperature is too high parameters dt and d defrost probe the manual defrost is not activated and the defrost LED flashes compressor protection times set parameter d9 select d9 1 the high temperature al...

Page 19: ...0 r2 Maximum set point value 0 150 50 c2 Minimum compressor off time 0 100 4 do Type of Defrost 0 4 0 dI Interval between defrost 0 199 6 dt End defrost temperature set point 50 127 65 dP Maximum def...

Page 20: ...for proper superheat 4 Condensing temperature too low 4 Check ambient temperature 50 F to 100 F Compressor 1 Operating beyond design conditions 1 Add equipment so that conditions are within allowable...

Page 21: ...230V Defrost Heaters 4313F 3 3 3 3 3 3 3 3 Outdoor Parts Fan Pressure Control 28917301 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Fan Temperature Control 5521R 1 1 1 1 1 1 1 1 1 1 1 1 Drain Line Heate...

Page 22: ...PRIMARY SINGLE PHASE PROTECTION PROVIDED PRIMARY SINGLE PHASE PROTECTION PROVIDED CCH CRANKCASE HEATER PFC PRESSURE FAN CYCLE SWITCH DLT DRAIN LINE THERMOSTAT DLH DRAIN LINE HEATER TFC TEMPERATURE FA...

Page 23: ...ACITOR HPS HIGH PRESSURE SWITCH PRIMARY SINGLE PHASE PROTECTION PROVIDED PRIMARY SINGLE PHASE PROTECTION PROVIDED CCH CRANKCASE HEATER PFC PRESSURE FAN CYCLE SWITCH DLT DRAIN LINE THERMOSTAT DLH DRAIN...

Page 24: ...URE SWITCH PRIMARY SINGLE PHASE PROTECTION PROVIDED PRIMARY SINGLE PHASE PROTECTION PROVIDED CCH CRANKCASE HEATER PFC PRESSURE FAN CYCLE SWITCH DLT DRAIN LINE THERMOSTAT DLH DRAIN LINE HEATER TFC TEMP...

Page 25: ...Heatcraft Refrigeration Products LLC makes no warranty expressed or implied of fitness for any particular purpose or of any other nature whatsoever with respect to products manufactured or sold by Hea...

Page 26: ...is a continuing effort we reserve the right to make changes in specifications without notice Heatcraft Refrigeration Products LLC 2175 West Park Place Blvd Stone Mountain GA 30087 P 800 321 1881 www h...

Reviews: