1
Installation and Operations Manual
Alarm Signals
MESSAgE
CAUSE
OUTPUTS
P1
Room probe failure
Compressor output according
to parameters “Con” and “COF”
P
Evaporator probe
failure
Defrost end is timed
P3
Third probe failure Outputs unchanged
P4
Fourth probe
failure
Outputs unchanged
HA
Maximum
temperature alarm
Outputs unchanged
LA
Minimum
temperature alarm
Outputs unchanged
HA
Condenser high
temperature
It depends on the Ac
parameter
LA
Condenser low
temperature
It depends on the bLL
parameter
dA
Door open
Compressor and fans restarts
EA
External alarm
Output unchanged
Alarm Recovery
Probe alarms P1, P, P3 and P4 start some seconds after the fault
in the related probe; they automatically stop some seconds after
the probe restarts normal operation. Check connections before
replacing the probe.
Temperature alarms HA, LA, HA and LA automatically stop as soon
as the temperature returns to normal values.
Other Messages
MESSAgE MEANINg
Pon
Keyboard unlocked
PoF
Keyboard locked
noP
In programming mode: none parameter is present in Pr1
On the display the selected probe is not enabled
noA
None alarm is recorded
Technical Data
CHARACTERISTIC
DESCRIPTION
Housing
self extinguishing ABS
Case
XR40CX/XR60CX frontal 3x74 mm;
depth 60mm
Mounting
XR40CX/XR60CX panel mounting in a
71x9mm panel cut-out
Protection
IP0
Frontal protection
XR40CX/XR60CX IP65
Connections
Screw terminal block ≤ ,5 mm
wiring
Power supply
according to the model: 1Vac/dc,
±10%; 4Vac/dc, ±10%; 30Vac ±10%,
50/60Hz, 110Vac ±10%, 50/60Hz
Power absorption
3VA max
Display
3 digits, red LED, 14, mm high;
Inputs
Up to 4 NTC or PTC probes
Digital input
free voltage contact
Relay outputs
compressor: SPST 8(3) A, 50Vac; SPST
16(6)A 50Vac or 0(8)A 50Vac
defrost: SPDT 8(3) A, 50Vac
fan (XR60CX only): SPST 8(3) A, 50Vac
or SPST 5() A
Data storing
on the non-volatile memory (EEPROM)
Kind of action
1B
Pollution grade
Software class
A
Rated impulsive voltage 500V
Overvoltage Category
II
Operating temperature
0÷60 °C
Storage temperature
-30÷85 °C
Relative humidity
0÷85% (no condensing)
Measuring and
regulation range
NTC probe: -40÷110°C (-40÷30°F)
PTC probe: -50÷150°C (-58÷30°F)
Resolution
0,1 °C or 1°C or 1 °F (selectable)
Accuracy (ambient
temp. 5°C)
±0,7 °C ±1 digit