Output Thermocouple
: The process (output) temperature is indicated
by the
PROCESS TEMPERATURE
value readout on the
System
Status
screen. Modify the current
“High Temperature Alarm Set
Point”
located on the
System Set Up
►
Alarm Set Points
screen. Set
the
“High Temperature Alarm Set Point”
value to just below the
PROCESS TEMPERATURE
reading on the
System Status
screen.
The
High Temperature Alarm
will trigger and the controller will disable
the heaters and send the unit into
STANDBY
mode. Return the
“High
Temperature Alarm Set Point”
to the original setting.
7. The Aquarius
D.I. Water Heating System with Recirculation Option is tested to
ensure optimum functionality and performance during recirculation.
a. The inputs and outputs of the pump and pump controller are checked
and verified.
b. Communication between the pump, pump controller, and Aquarius
control system are verified and checked for functionality.
c. The pump safeties and/or alarms are tested. This includes the Water
Leaks Alarm, which is standard on the Aquarius
D.I. Water Heating
System, to ensure that the supply of D.I. Water to the unit is shut off in
the case that a critical leak condition is present.
d. The unit is allowed to operate with the controller
“Process Temperature
Set Point”
set to a value below the maximum temperature possible with
the unit in Recirculation to ensure optimal temperature performance during
Recirculation.
e. All external signals to the Aquarius
D.I. Water Heating System are
tested.
f. The Aquarius
D.I. Water Heating System Pump Air Cooling System is
tested to ensure optimal pump performance.