17
World Leaders in Ultra-Pure Heating
www.heateflex.com
405 E. Santa Clara St., Arcadia, CA 91006-7218
O
: (626) 599-8566
F
: (626) 599-9567
5. Connect the air supply lines and the purge or relief/vent water lines if
necessary.
6. Install incoming electrical power from main fusible disconnect (customer
supplied) to electrical compartment prior to being powered on. For point-to-
point connections see the electrical schematic drawings in SECTION II of
this manual. All switches must remain in the OFF position. See the
equipment specifications section on the Quality Control Documentation for
current rating, operating voltage, and type rating.
a. Customer Supplied main fusible disconnect switch must utilize Type
J low peak fuses. Consult Equipment Specifications in the Quality
Control Documentation for recommended amperage rating.
b. If Lockout/Tagout option is selected, Fusible Disconnect is provided.
Refer to drawing section of this manual for more information.
c. If a stationary appliance is not fitted with a supply cord and a plug, or
with other means for disconnection from the supply mains having a
contact separation in all poles that provide full disconnection under
overvoltage category II conditions, means for disconnection must be
incorporated in the fixed wiring in accordance with the wiring rules.
Compliance is checked by inspection.
7. Supply the unit with process fluid (and air if necessary). (Refer to the Facility
Diagram in
SECTION II
for more information.)
8. Start-up-procedure
a. Be sure all electrical switches and/or circuit protectors are in the
OFF position.
b. The Customer is responsible for connecting the
Remote EMO
button (optional) according to the schematic diagram provided, or
using a jumper if no
Remote EMO
is to be used. (Maximum input
resistance is 600 Ohms)
c. Establish the minimum flow for your system; for information, see
the specifications sheet.
d. Turn-on Customer supplied Fusible Electrical Disconnect. Heater
power is available but the unit will not turn on.
e. Verify that the compact fused disconnect switch(s) are set to the
ON position. If light is detected on the compact fused disconnect
switch, the fuse(s) may be open and need replacing.
f. Turn on the unit (by pressing the
“ON”
button on the front of the
unit). The controller will load into the
“STANDBY”
mode. Please
note that the door must be completely closed in order for the unit to
turn ON.