background image

 

Heatilator • ICON DV-IDV Series • 4042-575 Rev G • 09/07 

5

G. Requirements for the Commonwealth of Massachusetts

NOTE: 

The following requirements reference various 

Massachusetts and national codes not contained in this 
document.

G. Requirements for the Commonwealth of 
Massachusetts

For all side wall horizontally vented gas fueled equipment 
installed in every dwelling, building or structure used in 
whole or in part for residential purposes, including those 
owned or operated by the Commonwealth and where the 
side wall exhaust vent termination is less than seven (7) 
feet above finished grade in the area of the venting, includ-
ing but not limited to decks and porches, the following 
requirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented 
gas fueled equipment, the installing plumber or gas fitter 
shall observe that a hard wired carbon monoxide detector 
with an alarm and battery back-up is installed on the floor 
level where the gas equipment is to be installed. In addition, 
the installing plumber or gas fitter shall observe that a 
battery operated or hard wired carbon monoxide detector 
with an alarm is installed on each additional level of the 
dwelling, building or structure served by the side wall 
horizontal vented gas fueled equipment. It shall be the 
responsibility of the property owner to secure the services 
of qualified licensed professionals for the installation of hard 
wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled 
equipment is installed in a crawl space or an attic, the hard 
wired carbon monoxide detector with alarm and battery 
back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can 
not be met at the time of completion of installation, the 
owner shall have a period of thirty (30) days to comply with 
the above requirements; provided, however, that during 
said thirty (30) day period, a battery operated carbon mon-
oxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance 
with the above provisions shall comply with NFPA 720 and 
be ANSI/UL 2034 listed and IAS certified. 

Signage

A metal or plastic identification plate shall be permanently 
mounted to the exterior of the building at a minimum height 
of eight (8) feet above grade directly in line with the exhaust 
vent terminal for the horizontally vented gas fueled heating 
appliance or equipment. The sign shall read, in print size no 
less than one-half (1/2) inch in size, 

“GAS VENT 

DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUC-
TIONS”.

Inspection

The state or local gas inspector of the side wall horizontally 
vented gas fueled equipment shall not approve the installa-
tion unless, upon inspection, the inspector observes carbon 
monoxide detectors and signage installed in accordance 
with the provisions of 248 CMR 5.08(2)(a)1 through 4. 

Exemptions

The following equipment is exempt from 248 CMR 
5.08(2)(a)1 through 4:

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall 
horizontally vented gas equipment provides a venting 
system design or venting system components with the 
equipment, the instructions provided by the manufacturer 
for installation of the equipment and the venting system 
shall include:

A copy of all installation instructions for all Product 
Approved side wall horizontally vented gas fueled equip-
ment, all venting instructions, all parts lists for venting 
instructions, and/or all venting design instructions shall 
remain with the appliance or equipment at the completion of 
the installation. 

See Gas Connection section for additional Common-
wealth of Massachusetts requirements.

•  Detailed instructions for the installation of the venting 

system design or the venting system components; and

•  A complete parts list for the venting system design or 

venting system. 

• 

The equipment listed in Chapter 10 entitled “Equipment 
Not Required To Be Vented” in the most current edition 
of NFPA 54 as adopted by the Board; and 

•  Product Approved side wall horizontally vented gas 

fueled equipment installed in a room or structure sepa-
rate from the dwelling, building or structure used in 
whole or in part for residential purposes.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall 
horizontally vented gas fueled equipment does not provide 
the parts for venting the flue gases, but identifies “special 
venting systems”, the following requirements shall be satis-
fied by the manufacturer:

•  The referenced “special venting system” instructions 

shall be included with the appliance or equipment 
installation instructions; and 

•  The “special venting systems” shall be Product 

Approved by the Board, and the instructions for that 
system shall include a parts list and detailed installation 
instructions. 

Summary of Contents for Gas Fireplace IDV4833IH

Page 1: ...ome and must be installed in accordance with the manufacturer s instructions and the manufactured home construction and safety standard Title 24 CFR Part 3280 or Standard for Installation in Mobile Ho...

Page 2: ...er s manual for future reference Congratulations on selecting a Heatilator gas appliance an elegant and clean alternative to wood burning appliances The Heatilator gas appliance you have selected is d...

Page 3: ...s 27 C Install the Heat Shield and Horizontal Termination Cap 28 D Install Roof Flashing and Vertical Termination Cap 30 E Assemble and Install Storm Collar 31 9 Gas Information 32 A Fuel Conversion 3...

Page 4: ...nts which refers to 15 U S Code USC 2063 stating Such certificate shall accompany the product or shall otherwise be furnished to any distributor or retailer to whom the product is delivered Some local...

Page 5: ...ilding at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in prin...

Page 6: ...ne Safety glasses Level Manometer Voltmeter Tape measure Non corrosive leak check solution 1 2 3 4 in length 6 or 8 self drilling screws Keep appliance dry Mold or rust may cause odors Water may damag...

Page 7: ...ons diagrams are not drawn to scale Actual installation may vary due to individual design preference Fire Risk Provide adequate clearance Around air openings For service access Locate appliance away f...

Page 8: ...iling base plate and cantilever floor of the chase should be insulated Vapor and air infiltration barriers should be installed in the chase as per regional codes for the rest of the home Additionally...

Page 9: ...d surfaces extending full width and depth of appliance Do NOT install appliance directly on carpeting vinyl tile or any combustible material other than wood WARNING Model A Rough Opening Width B Rough...

Page 10: ...1 4 22 22 3 4 30 in minimum to ceiling 1 2 10 10 3 4 Figure 3 3 Clearances to Mantels or Other Combustibles Above Appliance 1 in 25 mm min to perpendicular wall A 7 75 in 159 mm min from fireplace op...

Page 11: ...insulation or other materials away from vent pipe may cause fire Measure horizontal clearances from this surface Measure vertical clearances from this surface Figure 4 1 Clearances from Cap Surfaces s...

Page 12: ...now regions Storm Collar Roof Flashing Figure 4 2 Minimum Height from Roof to Lowest Discharge Open ing A Gas Termination Wood or Fuel Oil Termination B 6 in 152 mm min 20 in 508 mm min Direct Vent Ga...

Page 13: ...y open on a minimum of 2 sides beneath the floor N Vertical clearance between two horizontal termination caps 12 in 30 cm minimum O Horizontal clearance between two horizontal termination caps 12 in 3...

Page 14: ...A length of straight pipe is allowed between two 45 elbows see Figure 5 1 ALL vent configuration specifications MUST be followed This product is tested and listed to these specifications Appliance per...

Page 15: ...ly A maximum of three 90 elbows or six 45 elbows may be used in any vent configuration Some elbows may be installed horizontally See Figure 5 6 Elbows may be placed back to back anywhere in the system...

Page 16: ...25 ft max 7 62 m Figure 5 4 Minimum Installation Requirements for Two 45 Elbows Top Vent Horizontal Ter mination Top Vent Horizontal Termination Three Vertical Elbows See Figure 5 6 for information ab...

Page 17: ...tally Installed Vertically H2 Figure 5 6 Two or Three Elbows some Horizontal Note Subtract 3 ft 914 mm from the total horizontal measurement for each 90 elbow installed horizontally Subtract 1 1 2 ft...

Page 18: ...n No Elbows 12 ft 3 66 m min 60 ft 18 29 m max Maximum horizontal run is 100 of vertical but cannot exceed 26 ft 7 92 m Figure 5 10 Vertical Termination Two Elbows Figure 5 8 12 ft to 30 ft Vertical R...

Page 19: ...m horizontal run is 100 of vertical but cannot exceed 26 ft 7 92 m Figure 5 11 Vertical Termination Three Elbows some horizontal Note Subtract 3 ft 914 mm from the total horizontal measurement for eac...

Page 20: ...p insulation or other materials away from vent pipe may cause fire WARNING Figure 6 1 Minimum Top Vented DV Pipe Clearances 3 in 76 mm top clearance 1 in 25 mm clearance bottom sides 1 in 25 mm cleara...

Page 21: ...ceiling firestop may be installed above or below the ceiling Refer to Figure 6 5 Secure with three fasteners on each side Do not pack insulation around the vent Insulation must be kept away from the...

Page 22: ...rance Vaulted Ceiling Installation The attic insulation shield has been laser etched with cut lines and ceiling pitches to make field trimming easier Remove one shield from box Note Cut previously ins...

Page 23: ...liance as necessary It is acceptable to use wood shims Bend out nailing tabs on each side Keep nailing tabs flush with the framing Secure the appliance to the framing by using nails or screws through...

Page 24: ...ding two stories or High rise Applications For installation into a commercial multi family multi level exceeding two stories or high rise application All outer pipe joints must be sealed with high tem...

Page 25: ...2 Once both inner and outer flues are started press section A onto section B firmly until all lances have snapped into place Check to make sure they have snapped together see Figure 8 3 and the seams...

Page 26: ...e attached by fitting another pipe section to it and snapping it together as normal Assemble Slip Sections The outer flue of the slip section should slide over the outer flue of the pipe section and i...

Page 27: ...ipe rotate either section see Figure 8 10 so that the seams on both pipe sections are aligned see Figure 8 11 They can then be carefully pulled apart Figure 8 8 Securing Vertical Pipe Sections Figure...

Page 28: ...the termination cap There are two sections of the standard heat shield One sec tion is factory attached to the wall shield firestop The other section is factory attached to the cap See Figure 3 1 If...

Page 29: ...and CAN CGA B149 installation codes INTERIOR Heat Shield or Extended Heat Shield Wall Shield Firestop Heat Shield 1 1 2 in 38 mm min overlap EXTERIOR SHEATHING Vent depth from back of appliance to out...

Page 30: ...2 to 12 12 4 0 Over 6 12 to 7 12 1 25 Over 12 12 to 14 12 5 0 Over 7 12 to 8 12 1 5 Over 14 12 to 16 12 6 0 Over 8 12 to 9 12 2 0 Over 16 12 to 18 12 7 0 Over 9 12 to 10 12 2 5 Over 18 12 to 20 12 7 5...

Page 31: ...he brackets and tighten the nut to complete the storm collar assembly Make sure the collar is tight against the pipe section See Figure 8 17 Slide the assembled storm collar down the pipe section unti...

Page 32: ...13 mm T handle manual shut off valve and flexible gas connector are connected to the 1 2 in 13 mm control valve inlet If substituting for these components please consult local codes for compliance Pr...

Page 33: ...allation is complete all connections must be tightened and checked for leaks with a commercially available non corrosive leak check solution Be sure to rinse off all leak check solution following test...

Page 34: ...Incorrect wiring will override IPI safety lockout and may cause explosion WARNING C Intellifire Ignition System Wiring This appliance requires a 110 VAC supply to the appliance junction box for operat...

Page 35: ...Verify proper operation after servicing CAUTION Shock Risk Replace damaged wire with type 105 C rated wire Wire must have high temperature insulation WARNING Ignitor Flame Sensor Pilot Assembly GRN OR...

Page 36: ...ppliance with two screws Figure 10 2 Remove Two Screws From Bracket If the junction box is being wired from the INSIDE of the ap pliance Remove one screw that attaches access panel to column See Figur...

Page 37: ...Noncombustible Facing Diagram 11 11 Finishing Fire Risk Finish all edges and fronts to clearances and specifications listed in manual WARNING Appliance front may be covered with non combustible mater...

Page 38: ...use of a decorative screen front not provided with the appliance F Refractory All refractory internal to the firebox comes pre installed See Section 12 I for installation of bottom front and side refr...

Page 39: ...Align opposite end of log with white notched area in top of base log Repeat for each top log See Figures 12 1 through 12 6 Figure 12 1 Placing First Top Log ICON60I Figure 12 2 Placing Second Top Log...

Page 40: ...s Panel Assembly Removing Replacing Glass Assembly See Figure 12 8 Remove three outer refractory pieces as per instructions in Section I Remove the lower decorative front face by removing the four scr...

Page 41: ...side of the screen rod into the horseshoe shaped cradle see Figure 12 11 Rotate the right side of the rod up and into the cradle on the right see Figure 12 12 Note Make sure the outside screen eyelet...

Page 42: ...Install Side Refractories Locate right side refractory panel See Figure 12 17 Install rod in hole in glass frame top See Figure 12 18 Insert Pin Notch Figure 12 18 Insert Pin into Top Frame Insert Pin...

Page 43: ...iance has an adjustable air shutter which controls the primary air Adjustment of the air shutter may be neces sary to obtain optimal flame appearance This should be adjusted by a qualified installer a...

Page 44: ...ith an integral barrier to prevent direct contact with the fixed glass panel Do NOT operate the appliance with the protective barrier removed Contact your dealer or Hearth Home Technologies if the bar...

Page 45: ...the appliance WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life FOR YOUR SAFETY READ BEFORE LIGHTING 33631D...

Page 46: ...o NOT store flammable materials in the vicinity of the appliance Do NOT use gasoline lantern fuel kerosene charcoal lighter fluid or similar liquids in this appliance Combustible materials may ignite...

Page 47: ...ocker switch or wall switch to OFF position Remove ignitor wire I from module Place ON OFF rocker switch or wall switch in ON position Hold ground wire about 3 16 in away from I terminal on module If...

Page 48: ...ire harness is firmly connected to module D Damaged pilot assembly or dirty sensor rod Verify that ceramic insulator around the sensor rod is not cracked damaged or loose Verify connection from sensor...

Page 49: ...grilles control compartment Burner burner ports Risk of Fire Delayed ignition or explosion Exposure to combustion fumes Odors WARNING Handle glass assembly with care Note Clean glass after initial 3 4...

Page 50: ...foration Sand and repaint as necessary 2 Replace appliance if firebox has been perforated Burner ignition and operation 1 Verify burner is properly secured and aligned with pilot or ignitor 2 Clean of...

Page 51: ...er to Sec tion 3 B D E 1 in 25 mm 29 1 2 in 749 mm C A Gas Line Electric Line 9 7 8 in 251 mm 13 3 8 in 340 mm 2 in 51 mm 2 1 4 in 57 mm F 21 1 2 in 546 mm Figure 16 1 Appliance Dimensions 16 16 Refer...

Page 52: ...Termination Cap High Wind Includes storm collar and fastener pack PVK 80 Power Vent Kit DVP TV Vertical Termination Cap Includes storm collar fastener pack DVP TB1 Basement window well termination ca...

Page 53: ...12MI 3 to 12 in 76 to 305 mm DVP24MI 3 to 24 in 76 to 610 mm 10 1 2 in 267 mm 10 7 8 in 276 mm DVP45 45 Elbow 45 4 7 8 in 124 mm Assembled Height 24 in 610 mm Diameter 10 in 254 mm DVP AS2 10 in 254 m...

Page 54: ...625 mm 13 1 4 in 367 mm RF12M Roof Flashing Multi pak BEK Trap Cap Brick Extension 13 3 4 in 349 mm 5 in 127 mm 13 3 4 in 349 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7...

Page 55: ...use with IPI and DSI appliances only 1 in 25 mm 14 in 356 mm 3 8 in 10 mm 1 in 25 mm 7 1 4 in 184 mm 7 3 4 to 10 3 8 in 197 to 264 mm DVP FBHT Fire Brick Termination Cap 7 1 4 in 184 mm 5 1 4 in 133 m...

Page 56: ...mum Term Cap Effective Length Effective Length TRAP1 4 1 8 in 5 5 8 in 105 mm 143 mm TRAP2 6 3 4 in 10 5 8 in 171 mm 270 mm Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm The heat shiel...

Page 57: ...Components Diagrams con t 13 in 330 mm 15 in 381 mm 8 1 8 in 206 mm DVP HRC SS 10 7 8 in 276 mm 10 1 2 in 267 mm 3 87 Effective Length 5 3 4 to 8 3 8 in 146 to 213 mm 5 1 2 in 140 mm 8 3 8 in 213 mm...

Page 58: ...ervice Parts List IDV4833 SERIES Service Parts Exploded Parts Diagram Beginning Manufacturing Date Jan 07 33 in ICON Gas Appliance DV Ending Manufacturing Date Active 4 3 2 1 6 7 9 8 12 13 14 11 10 5...

Page 59: ...affle 4045 203 4045 203 4045 203 4045 203 1 16 Wire Assembly 593 590A 593 590A 593 590A 593 590A 1 17 Control Module 593 592 593 592 593 592 593 592 1 18 Battery Pack 593 594A 593 594A 593 594A 593 59...

Page 60: ...42 575 Rev G 09 07 Service Parts IDV4833 SERIES Exploded Parts Diagram Beginning Manufacturing Date Jan 07 33 in ICON Gas Appliance DV Ending Manufacturing Date Active 2 1 3 4 5 6 7 8 Front Refractory...

Page 61: ...042 454 4042 455 4042 454 4042 455 1 9 Front Hearth Refr 4042 466 4042 466 4042 466 4042 466 1 10 Left Front Refractory 4042 459 4042 463 4042 459 4042 463 1 11 Right Front Refractory 4042 458 4042 46...

Page 62: ...G 09 07 IDV6247 SERIES Service Parts Exploded Parts Diagram Beginning Manufacturing Date Jan 07 47 in ICON Gas Appliance DV Ending Manufacturing Date Active 4 3 2 1 6 7 9 8 12 13 14 11 10 5 15 33 16 1...

Page 63: ...ffle 4045 203 4045 203 4045 203 4045 203 1 16 Wire Assembly 593 590A 593 590A 593 590A 593 590A 1 17 Control Module 593 592 593 592 593 592 593 592 1 18 Battery Pack 593 594A 593 594A 593 594A 593 594...

Page 64: ...42 575 Rev G 09 07 IDV6247 SERIES Service Parts Exploded Parts Diagram Beginning Manufacturing Date Jan 07 47 in ICON Gas Appliance DV Ending Manufacturing Date Active 12 Log Grate Assembly 2 1 3 4 5...

Page 65: ...ractory 4042 467 4042 467 4042 467 4042 467 1 10 Left Front Refractory 4042 461 4042 465 4042 461 4042 465 1 11 Right Front Refractory 4042 460 4042 464 4042 460 4042 464 1 For Complete Log Set Assemb...

Page 66: ...orative front DF SAL47 BK Salem black decorative front DF SAL47 BZ Salem bronze decorative front WSK MLT HTL Multi function wall switch RC BATT HTL Remove control RC SMART HTL Remote control requires...

Page 67: ...ons inadequate ventilation or drafting caused by tight sealing construction of the structure air handling devices such as exhaust fans or forced air furnaces or other causes 5 use of fuels other than...

Page 68: ...34 5000162 5016609 5076254 5113843 5191877 5218953 5263471 5328356 5341794 5347983 5429495 5452708 5542407 5601073 5613487 5647340 5688568 5762062 5775408 5890485 5931661 5941237 5947112 5996575 60067...

Reviews: