13. Activator Quickstart Guides
13.1.1 M432(ETO2) Activator/Controller
• Control Unit must be mounted inside or in a water-tight enclosure if mounted outside.
• Control Unit must be located within distance of
sensor being used. Sensors can be extended
using 6x14-16AWG wire up to 650 feet.
• Wiring/setup for this guide is using one (1)
M433/M430 (ETOG) sensor. For other sensor(s)
or other situations, please consult the complete
user manual.
• Installation/Setup of the activator should
be done AFTER completion of installing the
SnowMeltz® system and the substrate is fully
cured/completed.
M432(ETO2) With Cover Removed
Fig. 13.1A
Fig. 13.1B
Fig. 13.1C
The system must not be turned on until the concrete has fully cured.
DO NOT USE SnowMeltz® TO CURE/DRY CONCRETE.
The following must be follower when mounting the
in-ground sensor (M433/M430):
• Sensor must be located in the area as the
SnowMeltz® system.
• Sensor head must be flush with the top of the
asphalt/concrete.
• Space the SnowMeltz® mat slightly to
accomodate the sensor head.
• Ensure that heating element does not touch or
cross the sensor head, wire, or conduit.
13.1.2 MOUNTING SENSOR HEAD