background image

6

5.0 COMMISSIONING

5.1   DO NOT switch on the electrical supply until the unit and ice bank have 

been filled with water and checked for leaks.

5.2   Fill ice bank as follows. Push the supllied 8mm tube (water supply) into 

connection marked “FILL ICE BANK” turn water supply on, this will let 
water enter in the ice container. As container fills you will see the clear 
tube at the rear of unit will start to fill, when it reaches the level notch (L) 
close tap. Remove 8mm tube and insert red ‘T’ cap, push 8mm tube water 
supply into connection marked “IN WATER BTM”. 

5.3   Check that all installation, electrical and plumbing requirements have been 

met.

5.4   Check that all water and electrical connections are tight.
5.5   Turn  on  the  water  supply  and  operate  the  outlet  tap  until  water  flows 

smoothly from the outlet. Flow will initially be erratic as air is purged from 
the cooling coil. It is recommended that the water is allowed to flow for 
a few minutes to flush through the filter, internal pipes, tank and fittings 
of  any  air,  dust  or  debris  that  may  have  accumulated  during  transit  or 
installation.

5.6  Check that the filler spout is positioned at an angle that does not cause 

water to over-spill the sink or drip tray.

5.7  The flow of the water from the outlet can be adjusted if necessary. To do 

this  unscrew  the  hexagonal  nut  locating  the  push  button  and  remove. 
Remove  the  push  button  to  reveal  a  slotted  adjustment  screw.  Rotate 
the adjustment screw anti-clockwise to increase the flow or clockwise to 
decrease the flow. When the required flow is achieved, replace the push 
button and secure using the hexagonal nut.

5.8   Adjust the thermostat by turning the adjustment screw clockwise with a 

small screwdriver (thermostat located on rear panel of unit) to position 3 
or 4.

FIGURE 3: THERMOSTAT ADJUSTMENT

5.9  Switch  on  the  electrical  supply,  check  the  compressor  and  cooling  fan 

come into operation. Allow the unit to run for several minutes to cool the 
stored water (time will depend on thermostat setting and temperature of 
mains water and the surrounding air).

COLDER

1 2 3

4

5

6

7

OFF

Summary of Contents for SUPERCHILL 30B

Page 1: ...SUPERCHILL 30B Fitting Instructions and User Guide...

Page 2: ...n or instruction concerning the use of the appliance by a person responsible for their safety Children should be supervised to ensure they do not play with the SuperChill unit The SuperChill unit does...

Page 3: ...nsor assembly should be periodically cleaned to prevent a build up of dust or dirt on the cooling fins 1 5 The chiller must be installed vertically on a level surface 1 6 If you have purchased an inli...

Page 4: ...iller must be installed inside a building DO NOT install outside or in a position where it could be influenced by inclement weather conditions 2 6 DO NOT install where the unit may be exposed to extre...

Page 5: ...must be allowed for removal and replacement of the filter cartridge Connection of the water supply to the chiller and filter assembly is by means of an 8mm outside diameter flexible WRAS listed plast...

Page 6: ...es to flush through the filter internal pipes tank and fittings of any air dust or debris that may have accumulated during transit or installation 5 6 Check that the filler spout is positioned at an a...

Page 7: ...umstances evaporation salts may have accumulated around the outlet points This should be cleaned with a proprietary scale remover approved for sanitary ware Ensure all traces of the cleaner are remove...

Page 8: ...ia a small pump 6 3 4 Start the pump and operate the outlet to allow the disinfecting solution to enter the chiller Allow approximately 4 litres of solution to enter the chiller to ensure the chilling...

Page 9: ...tank 6 High ambient temperatire 45 C 6 At high ambient temperatures it is normal for the unit to work continuosly Compressor works continuosly but water is not cold 1 Gas leak from the cooling system...

Page 10: ...the water chiller is not in use for long periods during the winter months set the thermostat to a higher position 9 2 If the SuperChill water chiller is fitted with an in line filter that will remove...

Page 11: ...tions The unit has been used only for chilling potable water The unit is not 4 guaranteed against damage by frost or due to the build up of scale The guarantee does not cover the filter 10 0 ENVIRONME...

Page 12: ...Mail sales ewh co uk SPD Units 9 10 Hexagon Business Centre Springfield Road Hayes Middlesex UB40 0TY Tel 020 8606 3567 Parts Center Tel 0845 2709800 www partscenter co uk Newey Eyre Specialist Produc...

Reviews: