J. Troubleshooting Your Swimming Pool Heat Pump: Error Codes 

1.  The most common problem reported is the heat pump showing a display but not 

running its fan and compressor. This is the time delay on start up. From pressing 
START/STOP there is a 2 – 3 minute delay before the fan and compressor start. 

2.  The second most common problem is insufficient flow through the heat pump indicated 

by EE 03. If your swimming pool filter has a multiport valve turn off the pool pump and 
turn the valve to “recirculate” , restart the pool pump and try the heat pump again. If this 
solves the problem make sure your sand filter is backwashed. 

3.  Another issue is not being able to operate the control panel at all. Look for a small 

padlock symbol on the display which means that the controls are locked. To release 
this press the up and down arrows together at the same time for about 5 seconds so 
that the padlock symbol disappears. 

4.  During the operating and defrosting process, the heat pump will yield a volume of 

condensed water. The condensed water from the cooling coil will drip from the bottom 
of the heat pump. Do not assume the condensed water is due to a fault or a leak in the 
heat pump. 

The table below shows error codes the heat pump may display 

Fault/Error 

Display 

Cause 

Action 

Water temperature 
in, sensor fault/error 

PP 01

 

Sensor interrupted or short circuited

 

Test line, sensor and 
socket. 
May have to be replaced

 

Water temperature 
out, sensor 
fault/error 

PP 02

 

Sensor interrupted or short circuited

 

Test line, sensor and 
socket. 
May have to be replaced

 

Coil 1 sensor 
fault/error

 

PP 03

 

Sensor interrupted or short circuited

 

Test line, sensor and 
socket. 
May have to be replaced

 

Coil 2 sensor 
fault/error

 

PP 04

 

Sensor interrupted or short circuited

 

Test line, sensor and 
socket. 
May have to be replaced

 

Ambient temperature 
sensor

 

PP 05

 

Sensor interrupted or short circuited

 

Test line, sensor and 
socket. 
May have to be replaced

 

Too high difference 
in 
temperature in/out.

 

PP 06

 

Water flow too low

 

Check valves, filter pump, 
filter and by-pass 

Heating up

 

PP 07

 

Water flow too low

 

Check valves, filter pump, 
filter and by-pass 

First frost proofing 
run

 

PP 08

 

Low out temperature

 

Empty system of water

 

Second frost 
proofing run

 

PP 09

 

Low out temperature

 

Empty system of water

 

Function error in 
system 1

 

EE 01

 

Function error in print card

 

Call technician

 

Function error in 
system 2

 

EE 02

 

Input voltage too low

 

Check main cable / 
electrician

 

Flow guard error

 

EE 03

 

Too small or too high flow

 

Check pool pump, piping, 
by-pass and ball cocks. 
Check technical spec

 

 

EE 04

 

 

 

Temperature 
fluctuations

 

EE 05

 

Water flow varying

 

Check pool pump and 
piping. Check valves, filter 
and by-pass 

Defrosting

 

Logo

 

Cold coil / element.

 

None. Normal function

 

Communication error

 

EE 08

 

Communication error between 
control panel and control

 

Check cable connection. 
Call technician

 

 

 

Summary of Contents for WBR-17.0H-A

Page 1: ...ompressor and a 5 year parts warranty on the titanium heat exchanger Please contact your supplying dealer in the event of a claim This heat pump is designed for domestic use between May and September...

Page 2: ...Connecting Pipe Work C Sizes D Starting the Heat Pump E Setting the Temperature F Checking the Status G Changing the Mode H Auxiliary Mode I Winterising and Maintenance J Troubleshooting Error Codes K...

Page 3: ...be able to tolerate this B Connecting Your Swimming Pool Pipe Work 1 The pool water is fed through the heat pump by a swimming pool pump 2 The heat pump must be installed after down stream the swimmin...

Page 4: ...HeatSeeker Swimming Pool Heat Pump Page 4 of 10 C Sizes of Your Swimming Pool Heat Pump WBR 17 0H A WBR 21 0H A S A 855 955 B 660 660 C 660 660 F 370 370 G 110 110...

Page 5: ...de Set Aux 3 After a few seconds the display shows ROOM and a temperature This is the temperature of the air surrounding the heat pump 4 Push the START STOP button and await the display to show the in...

Page 6: ...to the standby mode after a few seconds 5 Restart the heat pump by pressing the START STOP button 6 After the 2 3 minute delay the heat pump will re start with the new set temperature F Checking the...

Page 7: ...ection H Auxiliary Mode of Your Swimming Pool Heat Pump 1 The AUX button on the heat pump is not used 2 When pressed the AUX button may make a wavy line symbol appear and disappear on the display but...

Page 8: ...sensor fault error PP 01 Sensor interrupted or short circuited Test line sensor and socket May have to be replaced Water temperature out sensor fault error PP 02 Sensor interrupted or short circuited...

Page 9: ...1 Heating only 3 0 3 3 For technician only 09 Work method 0 0 May not be changed 10 Setting of water temp auto mode 30 C 30 C For technician only 5 With the exception of Parameter 01 setting the pool...

Page 10: ...roll Number of Fans 1 Input Power of Fan W 200 200 Fan Rotation Speed rpm 830 830 Noise Level dB 60 60 Water Connection inches 1 1 Water Flow Rate m 3 h 5 8 6 10 Water Pressure Drop KPa 16 16 Unit Dim...

Reviews: