INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR 

WARM AIR CURTAIN HEATERS 

Catalogue Numbers HSAC3000X & HSAC4500X 

 

PLEASE RETAIN THIS LEAFLET FOR FUTURE MAINTENANCE 

 

MODELS 

These units are 635mm 3kW & 4.5kW modular heaters designed for 

mounting above doorways and similar entrances, and may be used as 
space heaters.  990mm 4.5kW and 990mm 6kW modules are also 
available. 
 

MOUNTING

 

When mounted over a standard shop doorway the unit should be 
fitted as low as possible and not more than 2.3 meters from ground 
level.  A single unit will provide reasonable coverage for a one metre 

doorway, and for wider doorways units can be mounted end to end. 
 
The unit should be positioned so that the airflow is not obstructed by 
any part of the doorframe. 
 

 

 

 

 

INSTALLATION

 

Carefully unpack the unit and remove the top cover fixing screws.  
The heater may be mounted using the mounting bracket provided. 
 

Remove mounting bracket screws, allowing the mounting bracket to 
be removed from the unit.  Making sure that the mounting bracket is 
horizontal, fix the bracket to the wall using 4 x No 8 wood screws.  
Place the unit on the mounting bracket ensuring the washer is 
positioned as in diagram. 

 
Tighten screws to hold the unit at the required angle. 

 

 

 

Fig 2 

WALL BRACKET ASSEMBLY 

 

The heater may also be mounted directly onto a suitable wall or 
bearer by four No 8 wood screws through the holes provided in the 

back of the unit casing.  Keyhole slots are provided for the top two 
fixings (fig 1). 
 

ELECTRICAL CONNECTIONS

 

These units are suitable for connection to a 230/240 volt 50 Hz single 
phase ac supply, except for the 220 volt models.  The heaters 
consume 3kW & 4.5kW respectively at 240 volts when switched to 
the full heat position. 

 
Model HSAC3000X (see fig 2) – 3 kW 

Model HSAC4500X (see fig 3) – 4.5 kW 

The appliance should be connected to the supply via a circuit in 
which there is an all-pole switch.  Test for correct operation and 

refit the cover. 

Fig 1 - OUTLINE DRAWING 