7
www.hedefsan.net
01 Ocak 2015
PTC
11:Ptc
Active
Choose the PTC motor thermistor input setting.
ACTIVE
Activates it.
CANCEL
Deactivates it.
CONTACT FEEDBACK
12:Contact Feedback
Active
Set here the bypassing of the contact feedback error. The controller
card does not detect any contactor adhesion when it’s cancelled. If it is
canceled our company is not responsible.
ACTIVE
Activating the contact feedback error
CANCEL
Bypassing the contact feedback error
POSITION RESET
13:Position Reset
Cancel
Even when there’s a power blackout the controller card will remember
its last position. But in some special cases when the power returns, a
position reset may be wanted. In that case the elevator will go until it
reaches the 817 limit switch of the bottom floor. When it reaches the
bottom floor, the floor counter will reset. For example: with systems
that have battery charged rescuers, this parameter can be activated to
reset the position.
ACTIVE
Activates it.
CANCEL
Deactivates it.
REVISION LIMIT SWITCH
14:Rev. Limit Switch
Until limit switch
Set the movement type of the up and down limit switches in revision.
Until Limit switch
When limit switches are enabled the elevator will stop before reaching
its floor.
Until Floor
Even when limit switches are enabled the elevator will go to its floor.