Gas fired igniter ZT0
Installation and initial commissioning
Status: 11-2018
- 27 -
DANGER!
Explosion risk due to leaking fuel or release of
additional units!
Downstream units (e.g. burner/igniter) can be
connected via incorrect operation of the gas fired
igniter.
– The gas fired igniter, and the external flame
monitor signal of the gas fired igniter should be
incorporated into an overriding safety controller.
– On commissioning, it must be ensured that in
the case of a flame signal breakdown, the flame
signal contact opens within 1 s, and leads to
the safety and fault shutdown via the overriding
safety controller.
Definitions
REMARK!
Air inlet pressure/gas inlet pressure:
Air pressure, respectively gas pressure at the gas
fired igniter’s air or gas port.
Air operating pressure/gas operating pressure:
Permissible air pressure or gas pressure to
operate the gas fired igniter. Pressure to be picked
up at the air or gas pressure test nipple.