2 General
KRONOS 20
5
2.3
System Components
•
Gas control valve E-LES 30 / E-LES 50 / E-LES 80
•
Control unit KRONOS 20
•
Intake manifold pressure sensor with integrated temperature sensor P/T-S-01
•
Speed pickup IA…
•
Cable harness
cable to the digitally controlled main adjusting screw
sensor cable for P-/T sensor
speed pickup cable
communication cable between control unit and PC
•
Communications software DcDesk 2000
•
Optional
λ
sensor
•
Optional gas mixer from KRONOS 10
This system components may only be combined with gas mixers that meet
the HEINZMANN specifications. If a different gas mixer shall be used con-
sult HEINZMANN.
2.4
System Specifications
All ATEX certified components are suitable for zone 2.
Supply voltage
12 V DC or 24 V DC,
Min. supply voltage
10 V DC (E-LES 30/50)
18 V (E-LES 80)
Max. supply voltage
32 V DC
Residual ripple
10 % maximum at 100 Hz
Current consumption
max. 2 A
Admissible voltage drop at max.
max. 10 %
current drawing
Fuse (external)
6 A
λ
- range:
0.9..2.3
System is ready
10 s after energizing
Reaction time
100% deviation control in 0.3 s
Note