The system must be operated in a way to reliably exclude damage of any type.
In particular, the system may be operated only within the electrical and technical ranges indi-
cated in the specification.
Correct operation, damages and wear of all components should be checked regularly.
Concentration of hydrogen sulphide (H
2
S) in fuel must not exceed 0.1 %!
The gas must be dry!
When using biogasis used as fuel, gas bearing components and sections of
the system must be inspected twice a year!
To high residual concentration of hydrogen sulphide (H2S)or too much
residual humidity may cause corrosive effects that might block mechani-
cal componets. This might result in overspeed and serious damage to the
engine!
Gas valves E-LES might only be used as control valves!
Never use as shut-off valve!