13 Error Handling
60
KRONOS 20
- Check manifold temperature sensor and replace if required.
- Check tolerance values for manifold temperature sensor.
3019 ErrMeasuredPower
3119 SErrMeasuredPower
Cause:
- Short circuit or cable break at sensor input for measured power.
Response:
- Error message: Common alarm.
- Emergency operation with substitute value or last valid sensor value
depending on choosen response mode.
- Operation mode Open-Loop for emergency operation only if the substitute value.
for measured power is lower than the switch level for Closed-Loop mode.
- Error is cleared automatically when sensor values are within tolerances,
depending on choosen response mode.
Action:
- Check sensor cable for short circuit or cable break.
- Check power sensor and replace if required.
- Check tolerance values for power sensor.
3020 ErrLambda
3120 SErrLambda
Cause:
- Short circuit or cable break at sensor input for lambda sensor.
Response:
- Error message: Common alarm.
- Emergency operation in Open-Loop mode.
- Emergency operation with substitute value or last valid sensor value.
depending on choosen response mode.
- Error is cleared automatically when sensor values are within tolerances,
depending on choosen response mode.
Action:
- Check sensor cable for short circuit or cable break.
- Check lambda sensor and replace if required.
- Check tolerance values for lambda sensor.
3021 ErrCH4Content
3121 SErrCH4Content
Cause:
- Short circuit or cable break at sensor input for CH4-content.
Response:
- Error message: Common alarm.
- Emergency operation with substitute value or last valid sensor value.
depending on choosen response mode.
- Error is cleared automatically when sensor values are within tolerances,
depending on choosen response mode.
Action:
- Check sensor cable for short circuit or cable break.
- Check CH4-sensor and replace if required.
- Check tolerance values for CH4-sensor.
3046 ErrMisfireWarn
3146 SErrMisfireWarn
Cause:
- Speed variance has exceeded the power dependent warning curve for monitoring
of misfiring.
Summary of Contents for E-LES 30