13 Error Handling
62
KRONOS 20
3076 ErrParamStore
3176 SErrParamStore
Cause:
- Occurrence of an error on parameter programming of E
2
PROM.
Response:
- Error message: Emergency alarm by fatal error.
- Emergency operation possible with substitute value for valve position but not
advisible.
Action:
- Restart governor by a reset.
- Notify HEINZMANN.
3077 ErrProgramTest
3177 SErrProgramTest
Cause:
- Current monitoring of the programme memory reports an error.
Response:
- Error message: Emergency alarm by fatal error.
- Emergency operation possible with substitute value for valve position but not
advisible.
Action:
- Restart governor by a reset.
- Notify HEINZMANN.
3078 ErrRAMTest
3178 SErrRAMTest
Cause:
- Current monitoring of the working memory reports an error.
Response:
- Error message: Emergency alarm by fatal error.
- Emergency operation possible with substitute value for valve position but not
advisible.
Action:
- Note down the values of the parameters 3895
RAMTestAddr
and
3896
RAMTestPattern
as an extended error description.
- Restart governor by a reset.
- Notify HEINZMANN.
3080 ErrDisplay
3180 SErrDisplay
Cause:
- Error in display control.
Response:
- Error message: Common alarm.
- No communication with keyboard and disply on control unit.
Action:
- Restart governor by a reset.
- Notify HEINZMANN.
Note:
- Only at systems with keyboards and displays.
3081 Err5V_Ref
3181 SErr5V_Ref
Cause:
- The internal reference voltage 5 V is not within the permissible range
Response:
- Error message: Common alarm.
Action:
- Restart governor by a reset.
- Notify HEINZMANN.