13 Error Handling
KRONOS 20
63
3085 ErrVoltage
3185 SErrVoltage
Cause:
- The supply voltage for the governor is not within the permissible range.
Response:
- Error message: Common alarm.
Action:
- Restart governor by a reset.
- Notify HEINZMANN.
- Check voltage supply.
3090 ErrData
3190 SErrData
Cause:
- No data found or check sum over data is wrong oder read access E
2
PROM
reports an error.
Response:
- Error message: Emergency alarm by fatal error.
- Governor is operating by default parameters.
- Engine should not be started.
Action:
- Note down the values of the parameter 3099
EEPROMErrorCode
- Check data for correct setting, save parameters and restart control unit
by a reset.
- Notify HEINZMANN.
Note:
- This error will occur only after restart by by switch on the supply voltage or
when reseting.
3092 ErrConfiguration
3192 SErrConfiguration
Cause:
- Configuration of the programmed parameters are not plausible.
Response:
- Error message: Emergency alarm by fatal error.
- Emergency operation possible with substitute value for valve position but not
advisible.
Action:
- Write down the values of the parameter 3000
ConfigurationError
.
- Check data for correct setting, save parameters and restart control unit
by a reset.
- Notify HEINZMANN.
Note:
- This error will occur only after restart by by switch on the supply voltage or
when reseting.
3093 ErrStack
3193 SErrStack
Cause:
- Internal programming or computing error, “stack-overflow”.
Response:
- Error message: Emergency alarm by fatal error.
- Emergency operation possible with substitute value for valve position but not
advisible.
Action:
- Write down the values of parameters 3897
CstackTestFreeBytes
and
3898
IstackTestFreeBytes
.
- Restart governor by a reset