KRONOS 20
- Notify HEINZMANN.
3094 ErrIntern
3194 SErrIntern
Cause:
- Internal programming or computing error, so-called "EXCEPTION" error.
Response:
- Error message: Emergency alarm by fatal error.
- Emergency operation possible with substitute value for valve position but not
advisible.
Action:
- Write down the values of the parameters 3195
SExceptionNumber
,
3196
SExceptionAddrLow
, 3197
SExceptionAddrHigh
and 3198
SExceptionFlag
- Restart governor by a reset
- Notify HEINZMANN.