14 Parameter Description
70
KRONOS 20
14.2
List 1: Parameters
No. Name
Signification
1 TeethPickUp
Level:
4
Range:
1..400
Page(s):
Number of teeth of the measuring wheel for speed
pickup 1
21 SpeedOver
Level:
4
Range:
0..4000 1/min
Page(s):
Speed trip for emergency stop in case of overspeed
50 SpeedVarSampleSize
Level:
4
Range:
1..20
Page(s):
Signal for detection of speed deviation
51 SpeedVarFilterConst
Level:
4
Range:
0..100 s
Page(s):
Filter constant for detection of speed deviation
55 MisfireWarnDelay
Level:
4
Range:
0..100 s
Page(s):
Delay time for Warning due to Misfiring
56 MisfireEcyDelay
Level:
4
Range:
0..100 s
Page(s):
Delay time for Emergency stop due to Misfiring
255 StartSpeed1
Level:
4
Range:
0..4000 1/min
Page(s):
Minimum speed for detection of engine start.
Gas valve will be activated
256 StartSpeed2
Level:
4
Range:
0..4000 1/min
Page(s):
Minimum speed for detection of engine is running.
Monitoring speed pick up
314 StepperPosSecureMin
Level:
6
Range:
0..3650 steps
Page(s):
Lowest allowable gas valve position. Prevents hit of the
piston on lower end stop and resulting from that posi-
tion errors. Range depends on actual gas valve
315 StepperPosSecureMax
Level:
6
Range:
0..3650 steps
Page(s):
Highest allowable gas valve position. Prevents hit of the
piston on upper end stop and resulting from that posi-
tion errors.Range depends on actual gas valve
317 StepperPosOffset
Level:
6
Range:
0..3650 steps
Page(s):
Calibration value for gas valve position to match the
parametrized flow characteristics
Range depends on actual gas valve