14 Parameter Description
74
KRONOS 20
No. Name
Signification
1430 GasValveCorrFactor
Level:
4
Range:
1,5..4
Page(s):
Correction factor for geometry of the gas valve
1440 ZPRFullLoadDroop
Level:
2
Range:
0..10 mbar
Page(s):
Assumed pressure drop of the Zero pressure regulator at
rated Load
1441 ZPROffsetPressure
Level:
2
Range:
0..30000 Pa
Page(s):
Pressure offset of the Zero pressure regulator
1450 GasDensityConst
Level:
2
Range:
0,5..3 kg/m³
Page(s):
Constant gas density. At changing gas quality the cali-
bration value will be used
1451 CalorificValueConst
Level:
2
Range:
5..100 MJ/m³
Page(s):
Constant calorific value (LHV). At changing gas quality
the calibration value will be used
1452 LambdaStoichConst
Level:
2
Range:
1..30 m³/m³
Page(s):
Constant lambda stoichiom. value. At changing gas
quality the calibration value will be used
1460 LambdaTempCorrFactor
Level:
2
Range:
0..25 1/k°C
Page(s):
Correction factor for temperature dependant lambda
correction
1461 RefTemp
Level:
2
Range:
-100..1000 °C
Page(s):
Reference temperature for temperature dependant
lambda correction
1462 RichLeanMixtureCorr
Level:
2
Range:
0..400 %
Page(s):
Offset value for entire lambda map
1466 LambdaActValueFilter
Level:
4
Range:
0..100 s
Page(s):
Filter value for lambda value received from output po-
wer signal
1530 AnalogIn3_RefLow
Level:
4
Range:
0..22,7 mA
Page(s):
Low reference value of analogue input 3.
Standard for feedback signal (output power, lambda
sensor, CH4 content). Here set for 0..22,7 mA