5 System monitoring
Positioner DC 6-06
27
However even if the value returns to within a valid range, the error remains continuously
present if the 'freeze' is requested with4849
AnaStopHoldOrReset
= 1.
With these parameterization options, the appropriate error handling can be found for any
system.
5.5
Electronics monitoring
Electronics self-tests are performed to monitor the safe operating state. The following table
shows what is monitored and which errors are set in each case. The tests that are run once
when the control unit is booted are described in
10.7 Emergency shutdown errors
shows which errors lead to an emergency
shutdown of the system or which disable a system start. Each individual error is described
in detail in
Error Cause
3075
ErrClearFlash
Error when clearing the flash memory
(display in the bootloader)
3076
ErrParamStore
Error when storing parameters
3077
ErrProgramTest
Error in the ongoing test of the program memory
3078
ErrRAMTest
Error in the ongoing test of the RAM memory
3081
Err5V_Ref
Error at voltage reference values
3085
ErrVoltage
Operating voltage too high or too low
3089
ErrWatchdog
Undefined program flow, internal program error
(display in the bootloader)
3090
ErrData
No parameters available, or checksum of parameters is incorrect
(always active after a program download)
3093
ErrStack
Stack overflow, internal program error
3094
ErrIntern
Exception, internal program error
5.5.1
Voltage references
The PANDAROS DC 6-06 uses a voltage reference value for ratiometric measurement
at analogue inputs. The value must be within software-internal fixed limits or the error
3081
Err5V_Ref
is output and the setpoint input cannot be corrected.
5.5.2
RAM memory test
All of the used RAM memory is tested while the program is running. The address of the
cell that is being currently tested is shown in 3895
RAMTestAddr
. The test value that is
currently running can be taken from 3896
RAMTestPattern
. If a fault cell is detected,
these two displays are held, the error 3078
ErrRAMTest
is activated and a fatal error is
generated.