10
Error
handling
66
Positioner DC 6-06
3059 ErrFeedbackAdjust
3159 SErrFeedbackAdjust
Cause:
Automatic adjustment of the actuator could not be executed, incorrect input
in the reference values for the actuator (
Reaction: Control
unit
cannot be operated.
Action:
- Check the voltage supply and the supply leads to the actuator.
- Check the feedback cable to the actuator.
- Check the actuator, replace if necessary.
- To be able to run an automatic adjustment, the system must be stopped
- Check the reference values and error limits for the feedback
- Set the error limits
1952
FeedbackErrorLow
= 0
1953
FeedbackErrorHigh
= 65535
1956
FeedbackRefErrLow
= 0
1957
FeedBackRefErrHigh
= 65535
for the feedback, save the settings
Restart control unit and repeat the automatic adjustment.
- Set error limits again
Reference:
3060 ErrAmplifier
3160 SErrAmplifier
Cause:
Overcurrent in the actuator triggering.
Reaction:
- System cannot be started.
- Emergency shutdown.
Action:
Check the actuator, replace if necessary.
3075 ErrClearFlash
3175 SErrClearFlash
Cause:
An error has occurred while clearing the control unit's ROM.
Reaction:
- System cannot be started.
- Emergency shutdown.
Action:
- Restart control unit with
.
- Notify
HEINZMANN
.
Reference:
Note:
This error can only be seen in the bootloader.