Positioner DC 6-06
3085 ErrVoltage
3185 SErrVoltage
Cause:
The supply voltage for the control unit is not within the permitted range of
9 to 32 V.
Reaction:
- Error message.
- Errors clears itself if the voltage is within the normal range again.
Action:
Check the voltage supply.
3087 ErrMainCheckSum
Cause:
The checksum of the control unit program is wrong.
Reaction: Control
unit
cannot be operated
Action:
- Restart control unit with
.
- Notify
HEINZMANN
.
Reference:
Note:
This error can only be seen in the bootloader.
3089 ErrWatchdog
Cause:
Internal computing error, so-called “Watchdog error”
Reaction:
- Control unit cannot be operated
- Emergency shutdown.
Action:
- Restart control unit with
.
- Notify
HEINZMANN
.
Reference:
Note:
This error can only be seen in the bootloader.
3090 ErrData
3190 SErrData
Cause: Parameter
3099
EEPROMErrorCode
provides more information about the
type of error: