6 Inputs and outputs
Positioner DC 6-06
31
Switch function
Meaning
2810
SwitchStopRequest
0 = no stop request via digital input
1 = stop request via digital input
2828
SwitchErrorReset
0
1 = clear current error
(only with edge change)
2845
SwitchAutoAdjust
0
1 = automatic actuator adjustment
(only with edge change)
Table 8: Switch functions
6.1.1
Assignment of digital inputs
A digital input can be assigned to a switch function by entering the number of the digital
input in the corresponding assignment parameter of the function from 810
Funct...
.
An assignment of 0 means that the switch function is not being used by a digital input.
Such a switch function always has a value of 0 and is therefore always inactive.
A maximum of two digital inputs are available in the PANDAROS DC 6-06: Input 4 on
terminal 9 and input 5 on terminal 11. Consequently a maximum of two of the possible
switch functions can actually be used.
Switch function
Input
Remarks
0
not used, but analogue stop request is possible
810
FunctStopRequest
5
only possible when PWM setpoint and analogue
stop request are not simultaneously requested
0
not used, but error can be cleared with the PC
program or hand programmer
4 always
possible
828
FunctErrorReset
5
only possible when no digital stop is requested
0
not used, but auto adjust is possible with the PC
program or hand programmer or pressure switch
4 always
possible
845
FunctAutoAdjust
5
only possible when no digital stop is requested
Table 9: Switch function assignment