10
Error
handling
62
Positioner DC 6-06
10.5.2
Bootloader Communication
Communication between DcDesk 2000 or a hand programmer and the bootloader can
commence when the error lamp flashes.
In this condition, errors are indicated and it is also the starting point for the download of
a new control unit program (only with DcDesk 2000) which is basically performed by
the bootloader.
10.6
Configuration error
If the control unit is wrongly configured, this is shown in 3092
ErrConfiguration
. The
unit's configuration may be incorrect, for example, if the channel type is disregarded when
inputs or outputs are parameterized.
In addition to 3092
ErrConfiguration
, an error code appears in 3000
ConfigurationError
which tells you about the type of error. The display of 3000
ConfigurationError
changes
every second and shows all existing configuration errors.
The commu
n
ication program DcDesk 2000 displays the error text of
configuration errors in the “Current Errors” window.
Although it may be possible to clear a configuration error using the command “Clear
Error”, this does not remove the cause of the error. Most configuration errors are only
checked when the control unit is started, so a reset is required when the parameterization is
changed and the parameters are saved in the control unit.
The error codes and their meanings are given in the following tables. Whether one of the
listed communication protocols is implemented or not will depend on the particular control
unit firmware version. This means that not all of the errors listed here will occur in a
special control unit.
Note