10 Error handling
Positioner DC 6-06
63
Configuration error
10
Port is used as analogue input but not configured accordingly
15
Port is used as analogue output but not configured accordingly
20
Port is used as PWM input but not configured accordingly
25
Port is used as PWM output but not configured accordingly
30
Port is used as digital input but not configured accordingly
35
Port is used as digital output but not configured accordingly
40
The characteristic curve ActPosSetoint[FuelSetpoint] is not parameterized with a
rising characteristic
10.7
Emergency shutdown errors
The following list gives a summary of all the errors that either prevent starting or result in
an emergency shutdown during operation. The presence of at least one of these so-called
fatal errors will activate 3800
EmergencyAlarm
. These errors are described in detail in
Chapter
Error Cause
3050
ErrFeedback
Error in the actuator feedback
3056
ErrFeedbackRef
Error in the actuator feedback reference
3059
ErrFeedbackAdjust
Error in the actuator auto adjustment
3060
ErrAmplifier
Error in the amplifier
3075
ErrClearFlash
Error when clearing the flash memory
(display in the bootloader)
3076
ErrParamStore
Error when storing the E
2
PROM memory parameters
3077
ErrProgramTest
Error in the ongoing test of the program memory
3078
ErrRAMTest
Error in the ongoing test of the RAM memory
3089
ErrWatchdog
Undefined program flow, internal program error
(display in the bootloader)
3090
ErrData
No parameters, or checksum of parameters is incorrect
(always active after a program download)
3093
ErrStack
Stack overflow, internal program error
3094
ErrIntern
Exception, internal program error
An actuator auto adjustment (
8.1.2 Automatic calibration) cannot be
performed when a fatal error is present.
Note