10
Error
handling
64
Positioner DC 6-06
10.8
Error parameter list
The following error parameter list describes the causes of the individual errors and the
reaction of the control unit. It also indicates actions to rectify the errors.
The errors are entered in the current error memory starting from parameter number 3000
and in the permanent error memory starting from number 3100.
The errors are listed by ascending order of numbers, with the parameter on the left being
the current error in the volatile error memory and the one on the right the related parameter
in the permanent error memory. The control unit only reacts to current errors, the
permanent error memory is only used to collect errors which have occurred.
3000 ConfigurationError
Cause: Configuration
error.
Reaction: Display
Action:
Check the control unit configuration and rectify, save parameters and
perform a control unit reset
Reference:
3005 ErrAnaStopRequest
3105 SErrAnaStopRequest
3007 ErrFuelSetpAna
3107 SErrFuelSetpAna
3009 ErrFuelSetpPWMIn1
3109 SErrFuelSetpPWMIn1
3011 ErrFuelSetpPWMIn3
3111 SErrFuelSetpPWMIn3
Cause:
An error has occurred at the corresponding setpoint/sensor input (e.g. short
circuit or open circuit).
Reaction:
Depending on the configuration, the error may clear by itself when the
control unit's measured values are within the error limits again.
Action:
- Check the cable for short circuit or open circuit.
- Check the corresponding sensor and replace if necessary.
- Check the error limits for the sensor.
6.2.3 Error detection with the analogue inputs
-
5.3.1 Monitoring the analogue setpoint
-
6.3.2 Error detection with the PWM inputs
-
5.3.2 Monitoring the PWM setpoint