10 Error handling
Positioner DC 6-06
67
3076 ErrParamStore
3176 SErrParamStore
Cause:
An error has occurred while programming the control unit's parameter
memory.
Reaction:
- System cannot be started.
- Emergency shutdown.
Action:
- Restart control unit with
.
- Notify
HEINZMANN
.
3077 ErrProgramTest
3177 SErrProgramTest
Cause:
The continuous monitoring of the program memory returned an error.
Reaction:
- System cannot be started.
- Emergency shutdown.
Action:
- Restart control unit with
.
- Notify
HEINZMANN
.
3078 ErrRAMTest
3178 SErrRAMTest
Cause:
The continuous monitoring of the main memory (RAM) returned an error.
Reaction:
- System cannot be started.
- Emergency shutdown.
Action:
- Make a note of the settings of parameters 3895
RAMTestAddrHigh
and 3896
RAMTestAddrLow
- Restart control unit with
.
- Notify
HEINZMANN
.
3081 Err5V_Ref
3181 SErr5V_Ref
Cause:
The 5V sensor reference voltage 3603
5V_Ref
is not within the permitted
range of 4.5 to 5.5 V.
Reaction:
- Error message.
- Errors clears itself if the voltage is within the normal range again.
Action:
Check the sensor supply.