11 Parameter description
86
Positioner DC 6-06
Name
Meaning
4810 DigStopImplsOrSwitch
Level:
6
Range: 0/1
Page(s):
Activates the digital stop request as an impulse (1) or as
a switch (0)
(RESET)
4811 DigStopOpenOrClose
Level:
6
Range: 0/1
Page(s):
Activates the digital stop request as an NC (1) or NO
(0) contact
(RESET)
5000 CommAlarmLowActive
Level:
2
Range: 0/1
Page(s):
Selects whether the common alarm display will be low
active (0 when at least one error is present) or high
active (1 when at least one error is present)
5100 NoStoreSErrOn
Level:
6
Range: 0/1
Page(s):
Suppresses the storage of errors in the error memory
until the control unit is restarted
5102 CommonAlarmResetOn
Level:
2
Range: 0/1
Page(s):
Selects whether the common alarm display will be
briefly reset (edge change) when a new error is added
5103 CommonAlarmResetBoth
Level:
2
Range: 0/1
Page(s):
Selects whether the edge change (5102
CommonAlarmResetOn
= 1) is also generated when an
error disappears (generally with every error change)
5510 AnaStopCurrOrVolt
Level:
2
Range: 1..2
Page(s):
Selects the signal type of the analogue input for the stop
request
1: 0..5 V
2: 0..22.7 mA
(RESET)
5530 FuelSetpCurrOrVolt
Level:
2
Range: 1..2
Page(s):
Selects the signal type of the analogue input for the
setpoint generator
1: 0..5 V
2: 0..22.7 mA
(RESET)
5600 LowPowerEnable
Level:
2
Range: 0/1
Page(s):
Activates the enabling of undervoltage
5700 ActuatorTestOn
Level:
2
Range: 0/1
Page(s):
Activates the test mode for the actuator
This function cannot be stored