7 Maintenance instructions
Hekatron Smoke Switches are to be maintained in accordance with VDE 0833
Part 1 taking into account special ambient operating conditions. We recom-
mend that Smoke Switches are serviced in our works when they have been in
operation for 8 years. Under special ambient operating conditions (e.g. excessive
exposure, external influences, contamination etc.), servicing in our works may
be needed after a shorter period
By observing basic maintenance measures according to DIN 31051 in conjunction
with DIN EN 13306, the LRS 01 system should be kept permanently ready for
operation; it should be serviced annually as specified by the manufacturer.
Test aerosol 918/5 from HEKATRON is to be used for functional testing of Smoke
Switch ORS 210.
The interaction of all items of equipment and their technical condition must be
checked.
The inlet tube must be inspected visually at regular intervals. Any deposits
found must be removed. For visual inspection, the inlet tube must be removed
from the LKS 02 socket. After visual inspection and cleaning, the inlet tube must
be correctly replaced.
The Smoke Switch must not be opened!