Communication interface
Relay
contactso
Supply
voltage
5.2 Electrical connection of the ORS 210
At the cable gland and fastening, there must be no leakage to the ventilation
duct. When connecting or changing the socket, ensure that it is correctly ori-
entated to the direction of flow. In the LKS 02, the LED of the ORS 210 and the
arrow in the socket point towards the outlet tube. The LRS 01 can only operate
correctly when the cover is properly closed.
For cable entry, 4 x M16 plugs are fitted. When properly used, they comply with
the requirements of IP 54 within their 6 – 10 mm sealing range.
The sealing plugs can be replaced/supplemented by 16 x 1.5 cable glands with
M16 x 1.5 locknuts.
Terminal assignment in socket of LKS 02
Terminal 1
24 V DC
Terminal 2
0 V DC
Terminal 3
Option (communication/RS BUS)
Terminal 4 and 5
Potential-free NC
Terminal 6
free
Electrical installation
The electrical installation must comply with VDE regulations.
Safety instruction
Electrical connection is only to be carried out by a qualified electrician or
by a person suitably instructed in electrotechnical matters.
Operating positions of relay contacts
4
5
Operating status
- slight contamination
4
5
- heavy contamination
- no power
- fault
- alarm