Operating
46
Energy Manager 1.3 - Instruction Manual
Menu item
Display
Description
I/C
Legend:
*
Item is only displayed if the access level is service
I/C
Information / Command
Table 5-9 Solar submenu
5.1.10
Wind Submenu
Menu item
Display
Description
I/C
OpMode
1 of the modes:
Operating mode of the wind
system. The mode is also
displayed in the main menu if
no error occurred.
init
Software module initializes.
I
offline
Wind module is offline and will
not be started by the EM
control software
I
standby
Wind module is available.
I
error
Wind module is in error status. I
active
Wind module is running.
I
StateRpl
1 of the replies:
State reply. System answer to a
user command (CMD).
init
Software module initializes.
I
offline
Wind module is offline
I
run
Wind module is available and
will be used.
I
CMD
1 of the
commands:
Command to be entered by
user.
no command
No command in a queue.
I+C
go online
Start wind module
C
go offline
Stop wind module
C
cancel command Cancel command in queue.
C
Voltage
x.xx V
Wind voltage [V]
I
Current
x.x A
Wind current [A]
I
Power
x.x kW
Wind power [kW]
I
P-Meter
xxxx kWh
Wind energy [kWh]
I
Reset Counter*
Reset operating counters.
C*
Error List
Number in
hexadecimal
format
All active events are displayed
one after another with their
number and a short text and
can be confirmed.
I+C
Legend:
*
Item is only displayed if the access level is service
I/C
Information / Command
Table 5-10 Wind submenu