Getting Started
Energy Manager 1.3 - Instruction Manual
23
Port
Default sensor
Connection
DI2
Oil alarm (oil pressure)
DI3
Overheat alarm (water
temperature)
DI4
General genset alarm
DI5
Grid available signal
DI6
Door contact
DI7
Panic button
DI8
Motion sensor
DI9
Water sensor
DI10
Smoke detector
DI12
Genset 2 / grid – Genset run signal
AO1
GND 0-10V
FCU 1
AO2
GND 0-10V
FCU 2
- 100 VDC In 1
-100V
Voltage battery 1
- 100 VDC In 3
-100V
Voltage battery 2
AI1
0-20mA
Fuel1 level
AI2
10V
Current battery 1
AI3
10V
Current battery 2
AI4
10V
Current load 1
AI5
10V
Current load 2
AI6
10V
Current load 3
AI7
10V
Current load 4
AI10
30V
Genset 1 starter battery
AI11
5V
Solar
AI12
10V
Wind
A 20
30V
Genset 2 starter battery
T1
PT1000
Temperature shelter
T2
PT1000
Temperature outdoor
T3
PT1000
Temperature battery 1
T4
PT1000
Temperature battery 2
T5
PT1000
Temperature aircon 1
T6
PT1000
Temperature aircon 2
T7
PT1000
Temperature aircon 3
Table 4-2 Port assignment