Technical Data
Energy Manager 1.3 - Instruction Manual
67
10
Technical Data
Energy Manager
Designation
Definition
Specification
Physical data
Dimensions
Height 3 HU, Depth 19” W
305 x H 132 x D 483 mm
incl. handhold
Depth without handhold:
282 mm
Installation Depth
280 mm + Wiring
Weight
~ 5,9 kg (with battery ~ 7,2
kg)
Electrical
Supply Voltage
-36 to -72 VDC
19 to 36 VDC (optional)
100 to 240 VAC (optional)
Power Consumption
< 30 W
Operating
Temperature
0 to 50°C
Relative humidity
10 to 90% (non condensing)
Storage Conditions
-20 to + 85°C, 0 to 95%
Standards
EMC (CE)
EN 61000-6-1 & 6-3
Protection Grade
EN 60529 (IP20)
Connection Ports
Alarm Outputs / Dry
Contacts
16 Relay change-over
contacts, max. 0,5A / 230V
Analog Input
20 configurable 0-20 mA / 0-
5, 0-10, 0-30 VDC
4 voltage measurement -100-
0 VDC, 8 Pt 1000
Digital Input
12 electrical isolated
low level: 0-2 V
high level: 4-35V
Analog output
2 ports 0-10 VDC
Communication
Interfaces/Remote
Monitoring
Wireless
GPRS Quad band CS1-CS4,
CSD 9.6k; SMS
Ethernet
RJ 45 10/100 BaseT
Serial
RS 232, RS 485 (optional)
USB
2.0
Onsite Monitoring &
Control
Control
Panel 5 way keypad & 4-line
LCD-display configuration and
monitoring
Ethernet
Interface Advanced
configuration, monitoring