Getting Started
4.7
How to Ground the Energy Manager
In order to ground the Energy Manager, the ground cable must be
connected to the back of the Energy Manager. If a Genset is installed,
the other end of the ground cable is usually connected to the rectifier’s
grounding. It can also be connected to the rack’s or another ground.
Ground cable (green-yellow protective conductor, wire cross
section of at least 1,5 mm², 8 m in length, included in delivery).
The ground cable has been installed during site installation.
Ground the Energy Manager as follows:
1.
Tighten the earth circuit connector of the ground cable to the
grounding connection on the back side of the Energy Manager.
Figure 4-1 Grounding connection (1)
2.
Connect the other end of the ground cable to the desired grounding.
The Energy Manager is grounded.
4.8
How to Connect Power Supply
The power supply of the Energy Manager is connected to the priority load
of the rectifier, e.g. the battery.
2-pin cable
Small screw driver
Connector
NOTICE
Property damage due to incorrect polarity !
Incorrect polarity will permanently damage the device. Watch
out for correct polarity of the connection:.
Connect the power cable as follows:
Energy Manager 2.0 - Instruction Manual
29