Operating
5.1.4
Battery Submenu
Menu item
Display
Description
I/C
OpState
1 of the states:
Operational state of the
battery. The operational state
is displayed in the main menu
if no error has occurred.
init
Software module initializes
I
offline
Battery is offline and will not be
monitored by EM control
software.
I
error
Error detected, battery cannot
run.
I
blk charge
Battery charges with fixed
current
I
flt charge
Genset is running or site is
running on grid. Voltage is at
configured float voltage to
maintain voltage at floating
level (default: 54 V).
I
boost ch.
Battery charges with fixed
voltage.
I
discharge
Battery is in discharge.
I
eboost ch
Battery is in extended boost
charge and will be charged for
10 h (time is set in LAA).
I
equali ch
Battery is in equalization
charge and will be charged for
20 h (time is set in LAA).
I
v_sub_low
Battery is not charged or
discharged and the voltage is
below the float voltage.
I
OpMode
1 of the modes:
Operation mode that indicates
the system answer if a user
entered the change OPMode
command.
init
SW is initializing
I
run
User requested Online mode.
Theselected unit will switch to
one of the following
operational states:
-
Blk charge
-
Flt charge
-
Boost ch
-
Discharge
-
Eboost ch
-
Equali ch
-
V_sup_low
-
Error
I
48
Energy Manager 2.0 - Instruction Manual
Summary of Contents for Energy Manager 2.0
Page 1: ...Energy Manager 2 0 Instruction Manual ...
Page 6: ......
Page 14: ......
Page 78: ......
Page 93: ...Energy Manager 2 0 Instruction Manual 93 ...
Page 94: ......
Page 101: ...Heliocentris Industry GmbH Rudower Chaussee 29 12489 Berlin Germany http www heliocentris com ...