Air purifier AirPal Go 300/600 H
Installation and Operating Instructions
EN
EN
6
5�3 Unpack filter
m
Before commissioning the air purifier AirPal Go 300/600 H
for first time, it is necessary to disassemble the
filters from the set and remove the packaging / plastic from the high efficiency HEPA 14 absolute filter; it is
delivered totally protected in order to keep the filter‘s characteristics and properties intact (see Fig�3)
m
For any air purifier AirPal Go 300/600 H internal manipulation, is mandatory the use of suitable PPE *; mini-
mum mask and gloves� Each unit has two stickers (one on each removable filter cover) warning of the protec-
tion elements use before handling the unit� Once the filter protection has been removed, it must be placed back
into the corresponding slot (see Fig�4)
m
* In case of non-use of the PPE specified here, the absolute filter will lose its certification and filtration offe-
red, as well as the security provided by air purifier AirPal Go 300/600 H to avoid coming into direct contact with
viruses, bacteria, etc�
m
Do not use any similar or theoretically equivalent filter without previous consultation and authorization
from the manufacturer� In case of filter manipulation or changing by non-accepted units, the filtration guaran-
tee offered by the original air purifier AirPal Go 300/600 H will be lost�
See „8.4 Setup of filter replacing“ for filter
replacement frequency.
5�4 Configuration and setting of the ventilation level
Preconfigured parameters of the purifier control. The user must select the setpoint depending on the area [m²] where
the unit is going to be installed. The specifications apply to a 4-way air exchange. If a higher air exchange rate is to be
achieved, a correspondingly higher volume flow in relation to the area must be set.
m
We recommend a max. volume flow of 300 m³/h, otherwise the Hepa14 filter loses efficiency and separates less.
ATTENTION
Easy fastening system gives easy access
for filter replacement� An allan key is
required to loosen the handle before
rotation and to tighten the handle once
access is completed�
The H14 HEPA filter to be disassembled and
removed from their protection before com-
missioning and operation of the D (manda-
tory PPE use)�
Fig�3
Fig�4
ATTENTION
Air purifier AirPal Go 300 H
Surface
(m²)
Q max�
(m³/h)
Setpoint
Control voltage
(V)
Power
(W)
Current (A)
7,5
100
23
2,3
5,20
0,23
15
200
41
4,1
16,14
0,27
22,5
300
54
5,4
34,17
0,40
30
400
67
6,7
62,83
0,62
37,5
500
84
8,4
105,61
0,94
42,5
567
99
9,9
143,72
1,22
ATTENTION