28
Smoke exhaust fan control system –
EVS
Installation and Operating Instructions
5 .4 Error description Fault signals
Fault signals are delivered via the display on the front operating and display pad, on fireman‘s switches and pushbutton
alarms. There is also an option to forward the fault signal using the non-isolated contact in the EVS.
Possible causes for fault signals:
•
No mains power supply or main switch deactivated
•
Control fuse dropped, the low voltage power supply is defective
•
Motor monitoring device has triggered
•
Fault in detector circuits
•
Repair switch or system fault has triggered
The smoke exhaust fan is deactivated in ventilation mode. The smoke exhaust fan is not deactivated in smoke ventilation
mode. The signal must be unlocked on the motor protection device and the control unit after fault rectification.
Fault signals regarding the mechanical smoke extraction system must be indicated or forwarded in the building, so that they
are immediately recognised by users or the operator.
The cause of the fault signal must be immediately rectified in order to restore system functionality.
Fault
Cause
Solution
Visual fault indication and poten-
tial-free fault message (Passage
terminal 53/54)
Determine cause of fault via visual
diagnosis on circuit board (LED flashes
yellow)
FWS/BMA/DKM/RMR
• Short circuit or wire breakage in
detector circuit for FWS, BMA,
DKM, RMR (indicated as according
to diagnosis LED)
• No terminating resistor on last
detector in circuit
Check corresponding detector
circuit(s) and rectify the fault. Yellow
diagnosis LED goes out
TK/KL
Motor protection has triggered or wire
breakage. Diagnosis LED TK/KL lights
yellow
Check motor/motor protection (if
necessary, unlock)/check cable. Then
acknowledge using button TK/KL
Reset. Yellow diagnosis LED goes out
(if no motor protection connected,
unlock jumper
RepSW/Fuse
• Control fuse F1/F2 dropped
• Repair switch has been switched
or wire breakage between terminal
29/30
• Replace triggered control fuse.
Yellow diagnosis LED goes out
• Check repair switch or cable. If no
repair switch connected, insert jum-
per. Yellow diagnosis LED goes out.
Alarm/SysOFF
• Control system locked via input
terminal 31/32
• Control system deactivated via FWS
(LED FWS flashes simultaneously)
Check lock input (terminal 31/32) for
correct wiring. There must no inserted
jumper. Yellow diagnosis LED goes out
System switches to smoke extraction
although it has not been activated
No supply voltage
If necessary, connect power supply
Main switch deactivated
If necessary, activate main switch
Smoke detector detects smoke
Rectify cause and unlock control sys-
tem by deactivating the main switch
for at least 3 s.
No terminating resistor or wire breaka-
ge for detector circuit BMA. Diagnosis
LED lights red
Check detector circuit if BMA not
connected. Insert resistor at terminal
8/9
No low voltage 24 V DC at terminal
17/18
Control fuse F2 defective
Renew control fuse F2 and measure
low voltage between terminal 17/18
--> 24 V
Measured motor current is not consis-
tent with motor type plate
Mechanical motor defect
Check ventilation unit for mechanical
inhibition
Incorrect motor rotation direction.
Considerably higher current consump-
tion
Adjust motor rotation direction
Calculation error for star/delta
Setting current to I nom x 0.58
Potential-free fault message (Passage
terminal 53/54), but no visual fault
indication on front module
Front module connected incorrectly
Insert flat cable plug
Main switch deactivated
If necessary, activate main switch
No supply voltage
If necessary, connect power supply
Potential-free smoke extraction alarm.
(Passage terminal 50/51) although no
smoke extraction
Main switch deactivated
If necessary, activate main switch
No supply voltage
If necessary, connect power supply
EN
Summary of Contents for EVS Series
Page 9: ...7 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS D DE ...
Page 10: ...8 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS D DE ...
Page 11: ...9 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS D DE ...
Page 12: ...10 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS D DE ...
Page 13: ...11 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS SD DE ...
Page 14: ...12 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS SD DE ...
Page 15: ...13 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS SD DE ...
Page 16: ...14 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS SD DE ...
Page 17: ...15 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS DA DE ...
Page 18: ...16 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS DA DE ...
Page 19: ...17 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS DA DE ...
Page 20: ...18 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS DA DE ...
Page 21: ...19 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS W DE ...
Page 22: ...20 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS W DE ...
Page 23: ...21 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS W DE ...
Page 62: ...30 Smoke exhaust fan control system EVS Installation and Operating Instructions ...
Page 63: ...31 Smoke exhaust fan control system EVS Installation and Operating Instructions ...