CCR961 MANUAL-GB
22
Version B2:01-07-2015
5.2
Control of settings in each menu.
1.
The CCR is entered into
User Mode
(from Normal menu 1), by pressing:
>E<
Enter Code for User Mode
With >
< (arrow right) the menus are controlled/corrected as follows:
Menu
No.
Menu
Name
Default
Value
Comments
U1
Lamp alarm
Only for LAME adjustments (Point F)
U2
Std. L (Delta)
250
Only used in LAME minimum procedure
U3
Max lamps
40
Number of lamps in circuit
U4
Normal / %
50 %
No of faulty lamps as numbers or in %
U5
Lamp alarm
2 / 5
Alarm limit 1 and 2 to be set
U6
ISO Meas.
3 Hours
Time between ISO measurements
U7
ISO alarm 1
250K – 500K Set ISO alarm level 1
U8
ISO alarm 2
25K – 50K
Set ISO alarm level 2
U9 On-ref
band 0,5A
Accepted current deviation
U10 Imin
1,5A
U11 Step/
I out
1: 2,8A
2: 3,3A
3: 4,0A
4: 5,1A
5: 6,5A
6: 5,2A
7: 6,5A
8: 1,0A
Current values to controlled / adjusted
Step 8 is a special “black-current” step developed for Stopbarre
operation. Imin in step 8 reduced to 0,3A
U12
Interlock time 0 s
If interlock time is set > 0s, the CCR will automatically go back to
originally step after the set time in step 8.
If time set = 0s, no automatic return will take place from step 8.
U13
No. of Steps
5
No. of active steps to be set
U14 Uout
calibration
Uout
calibration
Must be performed after change of tapping on output transformer
U15 Uin
Uin
calibration
U16
Uin min. alarm 0V
Alarm limit for Uin.
The alarm level for Uin-alarm can be set between 304 and 380V.
If limit set to 0, the alarm is deactivated.
The alarm is delayed 2½ minute.
In case of alarm, the CCR will be switched-off, and the alarm must be
reset before the CCR can be switched-on again.
A special setting is activated by setting the limit to 300, and means:
CCR will be switched off (2½ min. delayed) if input voltage gets below
305V and will AUTOMATICALLY switch on again (10 s delayed)
when input voltage get over 323V.
U17 Display
Contr. 5
U18
Display light
7
Brightness adjustment
U19 Language
English
Select
display-language
U20
Circuit name
Name of series circuit is set
U21 User
password 0725
U22
Tapping contr.
Only valid for 400V input
U23 Z-alarm
Inactive
Recommended activated for circuits > 12,5KVA
U24
Ipeak start
Inactive
Default is soft start
U25
Watch calibr.
Factory setting is UTC
U26
Store data
New data stored by pressing >E<
Select default values by pressing >5<