CCR961 MANUAL-GB
24
Version B2:01-07-2015
5.3
Step by Step adjustments
Operation and adjustments can be performed in different menus, please consult 961.002 for more
details:
Normal Menu (no code) with the menus N1 – N7: Normal CCR operation and data read-out
User Menu (User code) with the menus U1 – U26: Standard user adjustments
Factory Menu (Factory code) with the menus F1 – F19: Special adjustments
To get access to the User or Factory menu, the CCR must be in menu N1 (where the Output
Current is shown), then press ”E”, followed by the relevant code, ending by pressing ”E” again.
Now you can change between the different menus by means of the push button right
or left
.
When all values are as wanted, go to the final menu to store the new values by pressing ”E”.
In the final menu, you could also select to eliminate the new adjustments by pressing ”C” or you
can select the factory default values by pressing ”5”.
An easy way to get to the final menu where the data are stored is to press arrow right
for some
seconds.
Remember, always save data changes when leaving the User menu (
>E< in menu U22)
or
leaving the Factory Menu
(>E< in menu F19).
Simple adjustments and operation instructions, “Step by step”
3.1.
Alarm acknowledge
3.2.
Manuel selection of intensity step
3.3.
Adjustment of number of intensity steps
3.4.
Adjustment of current in each step
3.5.
Reading of actual isolation value for the series circuit
3.6.
Adjustment of alarm limits for isolation level
3.7.
Adjustment of alarm limits for lamp failure
3.8.
Adjustment of time / date
3.9.
How to change the language in the display
3.10.
How to set up the name of the series circuit (f.i. RCL L1)
3.11.
Procedure for the change of a CCR module