CCR961 MANUAL-GB
26
Version B2:01-07-2015
3.4
Adjustment of number of intensity steps
The Key switch is turned to position ”Manual”
Press ”E”
Enter the code for User Menu
Press ”E”
Press
11 times to the display shows ”Max no. of steps”
Use the push-buttons 1 – 7 to select the number of active steps
Press
some seconds to get to the menu for ”Store data”
Press ”E”
3.5
Reading of actual isolation value for the series circuit
Press
3 times to get to the menu ”Circuit Isolation”. The value shown in the display may
be several hours old as the Isolation Value is only measured in certain intervals.
Pressing
will start a new measurement
After app. 10s, the new ISO value can be read in the display
3.6
Adjustment of alarm limits for isolation level
The Key switch is turned to position ”Manual”
Press ”E”
Enter the code for User Menu
Press ”E”
Press
6 times to see ”Circuit Isolation – Alarm 1” in the display
Use
to select the isolation value for the ”Alarm 1” limit
Press
once to see ”Circuit Isolation – Alarm 2” in the display
Use
to select the isolation value for the ”Alarm 2” limit
Press
some seconds to get to the menu for ”Store data”
Press ”E”
3.7
Adjustment of alarm limits for lamp failure
The Key switch is turned to position ”Manual”
Press ”E”
Enter the code for User Menu
Press ”E”
Press
4 times to see ”Lamp alarms” in the display
Press
and the value for ”Alarm 1” limit will start flashing
Use the push-buttons 0 – 9 to enter the desired value for alarm limit 1
Press ”E”
Press
and the value for ”Alarm 2” limit will start flashing
Use the push-buttons 0 – 9 to enter the desired value for alarm limit 2
Press ”E”
Press
some seconds to get to the menu for ”Store data”
Press ”E”
3.8
Adjustment of time / date
The Key switch is turned to position ”Manual”
Press ”E”
Enter the code for User Menu
Press ”E”