CCR961 MANUAL-GB
4
Version B2:01-07-2015
2
Overall CCR 961 information
2.1
Relevant standards
The range CCR 961 is constructed, manufactured and tested to meet the latest EN IEC 61822 standard.
The performance of the CCR 961 has been verified in tests performed by TÜV SÜD in Germany.
The range of CCR961 meets the requirements in ICAO Annex 14, as well as ICAO Design Manual
2.2
Main data
The CCR 961 in FAA layout is a complete unit including CCR Thyristor module for 40A, 60A or
110A, built together with output transformer and all belonging hardware such as measuring
transformers, Isolation Measuring equipment and lightning protection devices.
Standard power ratings from 2,2 KVA to 35 KVA.
Standard 100% series circuit current can be selected in the SW between 2,2A / 6,6A and 13,2A
(However, measuring transformer must be changed as well), but we can supply 8,3A – 10A – and 20A
versions as well.
Standard input voltages are 230V / 400V (± 10%) - 50Hz or 60Hz (± 2 Hz)
Features
Seven individual adjustable intensity
steps.
Earth fault supervision with two alarm
levels.
Lamp supervision with two alarm levels.
Hour meters for 100% intensity and total
time.
All CCR adjustment stored on changeable
Memory board for easy and fast
maintenance
Digital display showing:
Output current (RMS value).
Output voltage (RMS value).
Input voltage.
Time/date through build-in watch.
Power output.
Impedance to earth.
Number of faulty lamps
Mechanical specifications:
Height (mm)
Depth (mm)
Width (mm)
App. Weight
(KG)
CCR for 230V, Power rating
≤
10 KVA
1666
600
390
175 – 240
CCR for 400V, Power rating
≤
20 KVA
1666
600
390
175 – 275
CCR for 230V, Power rating > 10 KVA
1666
600
772
240 – 325
CCR for 400V, Power rating > 20 KVA
1666
600
772
275 – 325
Other specifications:
Max room temperature:
50 °C
Humidity, max:
95% (not condensing)
Efficiency:
230V supply 94 - 97%
400V supply 95 – 98%
Power factor better than 0,9 at full load (ohmish)
Cubicle is electro-plated and coated in light grey RAL 7035).