CCR961 MANUAL-GB
43
Version B2:01-07-2015
PD: 00100000
remote
Step = 2 (Emin1 alarm, Emin2 alarm (Emin = ISO))
Profibus master will send flg. data bit to CCR:
PA: 00000010
step 2
PB: 00000001
master, Status req.
Profibus module will send flg. data bit to master:
PC: 00000010
step 2
PD: 00100110
remote, Emin1 alarm, Emin2 alarm
Step = 2 (Imin alarm)
Profibus master will send flg. data bit to CCR:
PA: 00000010
step 2
PB: 00000001
master, Status req.
Profibus module will send flg. data bit to master:
PC: 00000000
PD: 00101000
remote, Imin alarm
Step = 2 (Imax alarm)
Profibus master will send flg. data bit to CCR:
PA: 00000010
step 2
PB: 00000001
master, Status req.
Profibus module will send flg. data bit to master:
PC: 00000000
PD: 00110000
remote, Imax alarm
Analog values:
I-out
:
Step = 2
Profibus master will send flg. data bit to CCR:
PA: 00000010
step 2
PB: 00010001
master, tx analog value type 0 (Iout)
Profibus module will send flg. data bit to master:
PC: 00011001
25 ~ Iout 2.5A
PD: 10000000
analog value type 0 ~ Iout
Lamp failure:
Step = 2
Profibus master will send flg. data bit to CCR:
PA: 00000010
step 2
PB: 00110001
master, tx analog value type 1 ~ lamp failure
Profibus module will send flg. data bit to master:
PC: 00000001
1 ~ lamp failure, one faulty lamp
PD: 10010000
analog value type 1 ~ lamp failure