Quickstart Guide PROFINET switch | Version 9 | 22.06.2020 

4.5

 

Further configuration and diagnosis via the web interface 

Via the web interface, the status of the PROFINET switch can 
be queried and further functions can be configured. 
Furthermore, a firmware update can be performed via the web 
interface. 

The web interface can be operated as soon as the device has a 
network configuration. The IP address of the device must be 
entered as URL. 

In the following login dialog the username is "admin" and the 
password is the serial number of the PROFINET switch which 
can be read at the device side. For the first login the default 
password must be changed. 

Further information about the web interface can be taken 
from the manual. 

 

5

 

 Diagnosis via LEDs 

PWR 

Off 

No power supply or device defective 

On 

Device is correctly supplied with voltage 

RUN 

On 

Device is ready to operate 

Flashing 

Device is starting up 

Flashing synchronous with 
BF and SF LED 

PROFINET function device identification 

BF 

On 

Bus error, no configuration 

Flashing synchronous with 
RUN and SF LED 

PROFINET function device identification 

SF 

On 

System error, network status in error 

Flashing synchronous with 
RUN and BF LED 

PROFINET function device identification 

RJ45 

LEDs 

Green (Link) 

Connected 

Orange (Act) 

Data transfer at the port 

 

 

 

Summary of Contents for 700-850-16PS01

Page 1: ...eg 2 91091 Großenseebach Germany 22 06 2020 Phone 49 9135 7380 0 Fax 49 9135 7380 110 info helmholz de www helmholz de Quick Start Guide PROFINET switch 4 8 16 port Order number 700 850 4PS01 700 850 8PS01 700 850 16PS01 Version en 9 ...

Page 2: ...or the use of the products described fulfills all safety requirements including all applicable laws regulations provisions and standards Intended use The device has a protection rating of IP 20 open type and must be installed in an electrical operating room or a control box cabinet in order to protect it against environmental influences To prevent unauthorized operation the doors of control boxes ...

Page 3: ...ROFINET switch 3 1 Connecting The PROFINET switch must be supplied with 24 VDC at the wide range input 18 30 VDC via the supplied connector plug The RJ45 sockets P1 P4 4 port switch P1 P8 8 port switch and P1 P16 16 port switch are used to connect the network devices PROFINET or Ethernet The inputs IN1 and IN2 have no function in the current firmware version yet and will be available for possible ...

Page 4: ...You can download the GSDML file from the website www helmholz de in the download area of the product or use the shown QR code You can find in the Manage general station description files dialog in TIA Portal in the menu Options PROFINET switch 4 port PROFINET switch 8 port PROFINET switch 16 port ...

Page 5: ...rk Components Helmholz GmbH Co KG Helmholz PN Switch Add the PROFINET Switch 4 port PROFINET Switch 8 port or PROFINET Switch 16 port device to the project and connect it with your PROFINET network By calling up the object properties you must assign the PROFINET switch a unique PROFINET name in the project and check the IP address for plausibility The real device must later be assigned the same na...

Page 6: ...e duplex TP 100 Mbps full duplex Fixed specification of the transmission rate This option is recommended when connecting PROFINET IO devices Monitor Send a diagnosis by Link Down Enable autonegotiation Automatic recognition of the transmission speed and the cable type cross or patch cable End of detection of accessible devices The DCP telegrams for recording accessible devices are not forwarded fr...

Page 7: ... switch is activated With the Update list button the network can be browsed for PROFINET participants The PROFINET device name can be assigned to the device with Assign name The clear identification of the PROFINET switch is ensured here by the MAC address of the device The MAC address of the device can be found on the device front of the PROFINET switch If the PROFINET switch has been assigned th...

Page 8: ...NET switch which can be read at the device side For the first login the default password must be changed Further information about the web interface can be taken from the manual 5 Diagnosis via LEDs PWR Off No power supply or device defective On Device is correctly supplied with voltage RUN On Device is ready to operate Flashing Device is starting up Flashing synchronous with BF and SF LED PROFINE...

Page 9: ...ch 16 x RJ45 integrated switch Features PROFINET Conformance Class B Media Redundancy MRP automatic addressing DCP topology detection LLDP diagnostic alarms Status indicator 4 LEDs function status 8 LEDs Ethernet status 4 LEDs function status 16 LEDs Ethernet status 4 LEDs function status 32 LEDs Ethernet status Voltage supply DC 24 V 18 30 V DC Current draw max 250 mA at 24 V DC max 110 mA at 24 ...

Page 10: ...se conditions We can send you the corresponding license conditions including a copy of the complete license text together with the product They are also provided in our download area of the respective products under www helmholz de We also offer to send you or any third party the complete corresponding source text of the respective open source software for an at cost fee of 10 00 Euro as a DVD upo...

Reviews: