background image

Quick Start Guide PN/CAN-Gateway CANopen®

10

10. LED status information

MODE

Off

No power supply or device defective

Blue on

PN/CAN-Gateway is correctly configured via PROFINET and

 

all CANopen® slaves are in Operational

Flashing blue

PN/CAN-Gateway is correctly configured via PROFINET and

 

at least one CANopen® slaves is in Pre-Operational or Stop or the gateway is not started.

Red on

No connection with PROFINET controller (PLC)

Flashing red

Connection with the PROFINET controller (PLC) exists, but a configuration error exists

CAN-RX

Flashing green

CAN frame is received without errors

Red

CAN bus error in the recipient or PN/CAN-Gateway hasn't been configured yet

CAN-TX

Flashing green

CAN frames are being transmitted

Red

Transmission not possible (e.g. false Baud rate, CAN bus disrupted) 
or PN/CAN-Gateway has not yet been configured

Summary of Contents for CANopen

Page 1: ...Quick Start Guide PN CAN Gateway CANopen www helmholz com Version 1en from FW 1 00 ...

Page 2: ...f the PN CAN Gateway 3 3 Plan PN CAN Gateway 4 4 Configure PN CAN Gateway 5 5 Add CANopen device 5 6 Configure CANopen device 6 7 Add PDOs process data objects 6 8 Assign the PN CAN Gateway a PROFINET name 7 9 Programming in the PLC 8 10 LED status information 10 11 Technical data 11 ...

Page 3: ...n basically configured Node ID device specific parameters PDO mapping etc 2 Preparation of the PN CAN Gateway 2 1 Connection The PN CAN Gateway is supplied via the 3 pin connection plugs with 24 V DC voltage The CAN bus is connected to the CAN interface using a SUB D plug e g Helmholz CAN bus plug The PROFINET line is connected to X1 P1 or X1 P2 The service USB interface is required for the firmwa...

Page 4: ...e catalogue under PROFINET IO Additional field devices Gateway Helmholz PN CAN Gateways Add the PN CAN Gateway CANopen device to the project and connect it with your PROFINET network By calling up the object properties you can assign the PN CAN Gateway a unique PROFINET name and check the IP address assigned by the system for plausibility ...

Page 5: ... CANopen master parameters Set the CAN Bitrate and the CAN Master Node ID In some applications a SYNC frame or heartbeat frame of the master is necessary for operation The other PN CAN CO slot entries contain no parameters 5 Add CANopen device A CANopen device is a CANopen slave An entry must be created for each CANopen slave ...

Page 6: ... RPDOs receive process data objects are sent by the PLC to the CANopen slave output data from PLC view The data size of the PDOs depends upon the data found in the PDO PDO mapping and can range between one and 8 bytes Which PDOs of which sizes the connected CAN device has can generally be determined in the manufacturer manual of the respective CANopen slave With the specification of the PDO number...

Page 7: ...y the IP address must be set To this purpose the function Edit Ethernet Node is used in the SIMATIC manager With the Browse button the net work can be browsed for PROFINET devices The clear identification of the PN CAN Gateway is ensured here by the MAC address of the device Important The assigned name must agree with the name defined in the hardware configurator If the PN CAN Gateway contains the...

Page 8: ...een switched off No CAN frames are being transmitted or received The CANopen slaves are stopped if the status was previously Operational value 2 1 If the previous status was 0 all CANopen slaves are initialized The status 1 is subsequently displayed in the Master state If the previous state was Operational 2 or Stop 3 only an NMT Pre Operational is transmitted 2 If the previous status was 0 all CA...

Page 9: ...tate 9 4 PDO data The PDO data is found as inputs TPDOs or as outputs RPDOs directly in the process map The inputs always show the last received data of the TPDO When changed values are written onto the outputs RPDO frames are sent to the corresponding CANopen slave 9 5 SDO communication SDO communication with the slaves can take place following the initialization phase of the PN CAN Gateway both ...

Page 10: ... is in Pre Operational or Stop or the gateway is not started Red on No connection with PROFINET controller PLC Flashing red Connection with the PROFINET controller PLC exists but a configuration error exists CAN RX Flashing green CAN frame is received without errors Red CAN bus error in the recipient or PN CAN Gateway hasn t been configured yet CAN TX Flashing green CAN frames are being transmitte...

Page 11: ...898 2 CAN High Speed physical Layer Connection 9 pin D sub male connector Protocol CANopen master as defined in DSP301 V4 2 Baud rate 50 100 125 250 500 800 1000 kbps Number of slaves 126 TPDOs RPDOs per slave 16 16 USB interface Protocol Full speed USB 2 0 device Connection Mini USB Electrically isolated from USB Yes insulation 1 5 kV Voltage supply DC 24 V 18 28 V DC Current draw Max 250 mA Dime...

Page 12: ...ssume no liability for any existing differences as these cannot be fully ruled out The information in this Quick Start Guide is however updated on a regular basis When using your purchased products please make sure to use the latest version of this Quick Start Guide which can be viewed and downloaded on the Internet at www helmholz com Our customers are important to us We are pleased to receive su...

Reviews: