Air Temperature Calibration in °C, value X 10, e.g. 1.0°C=10 

-

100 … 100

 

18 

1 byte 

Temperature Hysteresis in °C, value X 10, e.g. 0.5°C=5 

2 … 100

 

19 

1 byte 

Time correction by controller 

0, 1 

20 

1 byte 

Time format

։

 0=24 hour, 1=12 hour(am/pm) 

0, 1 

21 

1 byte 

Week Day 

1, 2, 3, 4, 5, 6, 7 

22 

1 byte 

Time: Hour and Minutes 

0 … 2359

 

23 

2 bytes 

Time Regulation ON time, min 

30 

10 … 240

 

24 

2 bytes 

Time Regulation OFF time, min 

30 

10 … 240

 

25 

1 byte 

Dry Time, min 

30 

5 … 90

 

26 

1 byte 

Mode to switch after Dry mode operation completion 

1, 2, 4, 5, 6 

27-40 

Reserved by manufacturer 

41 

2 bytes 

Morning start time. Format: HHMM. e.g.08:00 = 0800 

600 

0000 … 2359

 

42 

2 bytes 

Day start time. Format: HHMM. 

900 

0000 … 2359

 

43 

2 bytes 

Evening start time. Format: HHMM. 

1800 

0000 … 2359

 

44 

2 bytes 

Night start time. Format: HHMM. 

2300 

0000 … 2359

 

45 

2 bytes 

Monday Morning temperature, valueX10 

240 

10 … 370

 

46 

2 bytes 

Monday Day temperature, valueX10 

200 

10 … 370

 

47 

2 bytes 

Monday Evening temperature, valueX10 

230 

10 … 370

 

48 

2 bytes 

Monday Night temperature, valueX10 

180 

10 … 370

 

49 

2 bytes 

Tuesday Morning temperature, valueX10 

240 

10 … 370

 

50 

2 bytes 

Tuesday Day temperature, valueX10 

200 

10 … 370

 

51 

2 bytes 

Tuesday Evening temperature, valueX10 

230 

10 … 370

 

52 

2 bytes 

Tuesday Night temperature, valueX10 

180 

10 … 370

 

53 

2 bytes 

Wednesday Morning temperature, valueX10 

240 

10 … 370

 

54 

2 bytes 

Wednesday Day temperature, valueX10 

200 

10 … 370

 

55 

2 bytes 

Wednesday Evening temperature, valueX10 

230 

10 … 370

 

56 

2 bytes 

Wednesday Night temperature, valueX10 

180 

10 … 370

 

57 

2 bytes 

Thursday Morning temperature, valueX10 

240 

10 … 370

 

58 

2 bytes 

Thursday Day temperature, valueX10 

200 

10 … 370

 

59 

2 bytes 

Thursday Evening temperature, valueX10 

230 

10 … 370

 

60 

2 bytes 

Thursday Night temperature, valueX10 

180 

10 … 370

 

61 

2 bytes 

Friday Morning temperature, valueX10 

240 

10 … 370

 

62 

2 bytes 

Friday Day temperature, valueX10 

200 

10 … 370

 

63 

2 bytes 

Friday Evening temperature, valueX10 

230 

10 … 370

 

64 

2 bytes 

Friday Night temperature, valueX10 

180 

10 … 370

 

65 

2 bytes 

Saturday Morning temperature, valueX10 

240 

10 … 370

 

66 

2 bytes 

Saturday Day temperature, valueX10 

200 

10 … 370

 

67 

2 bytes 

Saturday Evening temperature, valueX10 

230 

10 … 370

 

68 

2 bytes 

Saturday Night temperature, valueX10 

180 

10 … 370

 

69 

2 bytes 

Sunday Morning temperature, valueX10 

240 

10 … 370

 

70 

2 bytes 

Sunday Day temperature, valueX10 

200 

10 … 370

 

71 

2 bytes 

Sunday Evening temperature, valueX10 

230 

10 … 370

 

Summary of Contents for HE-HT01

Page 1: ...HEATING THERMOSTAT HE HT01 USER MANUAL for Hardware v 12 Firmware v 2 2...

Page 2: ...k 9 Adding to Z Wave network 9 Removing from Z Wave network 9 Security 9 SmartStart 9 Firmware OTA Update 10 Z Wave Plus V2 Specifications 10 Associations 11 Settings Menu 11 Settings available throug...

Page 3: ...ng it always easy to read Highly configurable with automatic safety You can select one of six operation modes with individual set points either manually or by using a Z Wave controller gateway As a sa...

Page 4: ...NTC sensors range 1k to 100k Periodic measurements from o Internal temperature sensor o External floor temperature sensor o Internal humidity sensor o Internal ambient light sensor o Energy consumptio...

Page 5: ...ve the display unit and backplate of the HE HT01 from the packaging 3 FIRST ENSURE THE POWER IS OFF at the main circuit breaker and then test the wires with a probe or multimeter to verify Insert the...

Page 6: ...xt switch On the main power at the circuit breaker see photo above The HE HT01 will start up showing the original default factory settings 8 Remove the clear protective film from the display unit and...

Page 7: ...s for Morning Daytime Evening and Night For example the Morning Schedule could be set to 22 0 C starting at 6 00 The Day Schedule could then be set to 17 0 C at 9 00 when everyone has gone to work or...

Page 8: ...from all or part of the property for a length of time The factory default ECO Set Point is 20 0 C Note In your Z Wave gateway this mode will be shown as Energy Save Heat VAC Vacation Mode Away Use Va...

Page 9: ...wn 3 The current state of the network will display in the Parameter Value position upper right It should display InC Note If E L is displayed the HE HT01 is already Excluded 4 Start the Exclusion Mode...

Page 10: ...nauthenticated or S0 Association Group Info V3 highest granted S2 Authenticated S2 Unauthenticated or S0 Multi Channel Association V3 highest granted S2 Authenticated S2 Unauthenticated or S0 Thermost...

Page 11: ...corner of the LCD The top left corner will display the Parameter Number And the top right corner will display the Parameter Value To scroll through the menu press the Heating Element button to go up...

Page 12: ...cy list below Modification is possible only while the HE HT01 is not included to Z Wave network While the device is included the Antenna Icon is shown at the bottom right corner of the LCD main screen...

Page 13: ...e from the device menu Parameter 04 LPc Energy Consumption values This Parameter allows you to check the Cumulative and Real Time Energy Consumption of the connected load Display information follows t...

Page 14: ...h IDLE state OFF when the external input is open released If Parameter value 2 the external input will operate in Toggle Switch Reverse mode if the external input is shorted the Thermostat switches to...

Page 15: ...even though the floor temperature is higher than 30 C d If the room temperature is higher than 27 C the Heating Thermostat will enter IDLE mode even though the floor temperature is lower than 30 C Fac...

Page 16: ...set the value 12 The factory default value is 0 5 C 5 through Z Wave network Time Configurations Parameter 19 tCr Time Correction by Main Controller If this Parameter value 1 and the HE HT01 is connec...

Page 17: ...142 Note In order not to increase traffic on your network it is not recommended to reduce the value of this Parameter We recommend reducing the value of this Parameter only in case of poor connection...

Page 18: ...and is received If the Basic Set command value is 0 OFF state the HE HT01 will go to Manual MAN mode and switch Off the heating element IDLE mode If the Basic Set command is value is 0xFF ON state the...

Page 19: ...70 50 2 bytes Tuesday Day temperature valueX10 200 10 370 51 2 bytes Tuesday Evening temperature valueX10 230 10 370 52 2 bytes Tuesday Night temperature valueX10 180 10 370 53 2 bytes Wednesday Morni...

Page 20: ...be sent to you EXCEPT AS MAY BE OTHERWISE PROVIDED BY APPLICABLE LAW THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER COVENANTS AND WARRANTIES EITHER EXPRESS OR IMPLIED INCLUDING WITHOUT LIMITATION ANY I...

Reviews: