14
Temperature Sensor Calibration
Parameter 17
– Air Temperature Calibration
This parameter defines the offset value for room air temperature. If the internal air temperature sensor is not correctly
calibrated, then manual calibration can be made by adjusting the values up to ±10°C. This value will be added or
subtracted from the internal air temperature sensor reading. The value of this Parameter should be x10, e.g. for 1.5°C
set the value 15. The factory default value is 0
Time Configurations
Parameter 19
– Time Correction by Main Controller
If this Parameter value = 1 and the HE-TPS04 is connected to a Z-Wave gateway, the HE-TPS04 time and day will be
periodically polled and corrected from the gateway. To switch off auto-correction set the Parameter value to 0. The
factory default value is 1.
Parameter 21
– Day of the Week Manual Adjustment
This Parameter allows manual adjustment of the day of the week in case the HE-TPS04 is not connected to any Z-
Wave gateway or auto-correction is disabled (Parameter 19 value is 0). 1 = Monday, 2 = Tuesday, 3 = Wednesday, 4 =
Thursday, 5 = Friday, 6 = Saturday, 7 = Sunday. The factory default value is 1.
Parameter 22
– Time Manual Adjustment
This Parameter allows manual adjustment of Time. The Parameter has the following format: HHMM, where HH is hours
and MM is minutes. E.g. for 16:08 set the value 1608 and for 1:00 set the value 100.
Backlights Control Source
Parameter 30
– Buttons Backlight Color
Choose the value “1” if you wish the backlight active state to be blue, and the inactive state to be red (default). Choose
the value “0” if you wish the backlight active state to be red, and the inactive state to be blue. The factory default value
is 1.
Parameters 31-34
– Buttons Backlight Control Source
0
– Backlight is disabled (both color LEDs are turned off)
1
– Backlight is controlled by touch button (reflects the button state)
2
– Backlight is controlled by gateway or associated device (the button state is ignored)
Set the value for Button 1 in Parameter 31, for Button 2 in Parameter 32, for Button 3 in Parameter 33, for Button 4 in
Parameter 34. The factory default value is 1.
Note:
If the backlight is disabled (the P
arameter value is set to “0”), it is also impossible to control it from the gateway.
Buttons Mode
Parameters 41-44
– Buttons Hold (Long Press) Control Mode.
0
– Hold function is disabled
1
– Operate like click
2
– When the button is held the relay output state is ON, as soon as the button is released the relay output state changes
to OFF (momentary switch).
3
– When the button is held the relay output state is OFF, as soon as the button is released the relay output state
changes to ON (momentary switch).
4
– When the button is held or released the relay output state will toggle its state (ON to OFF or OFF to ON).
Set the value for Button 1 in Parameter 41, for Button 2 in Parameter 42, for Button 3 in Parameter 43, for Button 4 in
Parameter 44. The factory default value is 2
Note:
Regardless of this Parameter, the device will send scene notifications about the touch state (pressed, held,
released) to the gateway.
Parameters 51-54
– Buttons Click (Short Press) Control Mode
0
– Press function disabled
1
– Relay inverts state (toggles ON to OFF, OFF to ON) according to the relay state
2
– Relay inverts state (toggles ON to OFF, OFF to ON) according to the button backlight state.
3
– Relay switches to ON state only
4
– Relay switches to OFF state only
5
– Timer: On>Off Mode: Relay output switches to ON state (contacts are closed) then after a specified time switches
back to OFF state (contacts are open). The time is specified in Parameters 71-74.