background image

Helvar

 | Data is subject to change without notice.

www.helvar.com   

www.helvar.com   

Helvar 458Mx Chassis: Installation Guide

WARNING:

4.  Remove knockouts as required.

With the blanking plate(s) removed, the chassis is ready for a module 

to be attached (see diagram on page 3).

5.  If you are attaching a module, unscrew and remove the blanking 

plate(s).

Note:

 

458M1: 1 blanking plate

 

458M2: 2 blanking plates

 

458M3: 3 blanking plates

Note 1: The diagrams on this page show the 458M1/4S10 Chassis.

Covers and knockouts are removed from the 458M2 and 458M3 in a similar way.

Note 2: Use the grommets provided to protect cabling entering the knockouts.

If necessary, the knockout gland plates (on 458M2 and 458M3 types) can be removed to provide more 
space for cabling.

2. Mount to Wall

Mounting, Environmental and Clearance Requirements

Mounting

•  Mount the chassis vertically on a flat surface.
•  Use No. 8 or No. 10 screws with a head diameter between 6 mm and 9 mm.
•  Use wall plugs if necessary.
•  Mount chassis on wall using:

 

– 4 screws for the 458M1 and 458M2 chassis

 

– 6 screws for the 458M3 chassis

Environment

•  The ambient temperature must be between 0 ºC and +40 ºC.
•  Air humidity must be between 0 % and 90 % (noncondensing). 
•  The area must be adequately ventilated.
•  Do NOT install this product in a damp location.

Clearance

•  Make sure that enough space is left for ventilation and for attaching module(s): at least 5 cm above, 

below and to the right of the chassis, and 10 cm to the left. See ‘Mounting Dimensions and Clearance’ on 
page 4.

•  Leave sufficient clearance to allow cables and trunking to be connected.
•  When a Helvar module (e.g. a dimmer unit) is attached, the grilles must NOT be obstructed.

Heat sink

Grilles

Module grilles and heat sink

1. Remove Cover, Knockouts (and Blanking Plates)

Procedure

1.  Open the door and remove the screws (

A

 and 

B

) from the 

inside door.

2.  Remove the screws that are located to the left of the door (

C

 

and 

D

)

Note:

 

458M1: 2 screws (

C

 and 

D

)

 

458M2: 3 screws

 

458M3: 4 screws

3.  Remove the cover from the chassis.

Blanking

plate

Knockouts

Knockouts

THE BLANKING PLATE(S) PREVENT(S) ACCESS TO MAINS WIRING WHEN THERE 

IS NO MODULE CONNECTED.

DO NOT REMOVE THE BLANKING PLATE(S) UNLESS YOU ARE ATTACHING A 

MODULE.

A

C

B

D