Intelligence Aided Lifting Equipment
42
open contact of the clamp feedback switch, and link Pin 10 and Pin 6 to the normally
closed contact of the release button, and link Pin 4 and Pin 1 to the outer coil KM1 (such
as relay). In the “Extended Interface Settings”, set IO number of the clamp signal
feedback to 12, release signal input to 13, and release signal output to 24.
Note:
The coil power output from the handle extension interface shall be no higher than 12W.
The output of the expansion board is output of the relay contact.
5.6 Auto homing function
This function allows the equipment to automatically return to the pre-set homing position at
the set homing speed by triggering the auto homing signal. To enable the automatic homing
function, the automatic homing load weight and homing speed must be set first. The device will
not automatically return to home poison or stop the homing motion if the device meets with
resistance (causing the load weight more than the pre-set 15KG) when the homing function is
activated or during its homing action.
Note:
Set the homing speed to 5 in “Lifting Speed Adjustment” → “Speed Setting” → “Homing
Speed Setting”.
5.6.1
Homing Weight Setting
1.
Enter the “Extended Function Setting”
→
“Homing Setting” menu.
2.
Enter the submenu of “Fixture Weight” from the menu of “Homing Setting”, and then
press “ENT” button to record the homing weight (the maximum homing weight can be
set to 60KG) when the equipment is hung with the homing load and remains stable.
5.6.2
Usage method
Automatic homing signals can be input by the can be input through interfaces on the host
extension board, handle extension board, or expansion board. Set the corresponding IO number in
“Extended Function Setting” → “Expansion Interface Setting” → “Auto Homing”.
For example:
Take Pin 11 of the handle extension interface as the auto homing
signal input
terminal. Connect Pin 11 and Pin 6 of the handle extension interface to the normally open contacts
of the switch (self-recovery), and then set the IO number to 14 in “Switch to Double Limit”. When
the switch contact is open, the equipment returns to the homing position at the homing speed
5.7 Palletizing function
This function can realize the level-to-level precise stop of lifting equipment through the input
of palletizing signal. Before using this function, users need to set the layer height in advance, and
then the loads automatically stops running when the operating handle is moved up or down to the