Pressure Transmitters 050D series
Operating Instructions
- English - V1.0
PN-TI118-EN-14-1/17
Hengesbach GmbH & Co. KG
·
Schimmelbuschstr. 17
·
40699 Erkrath
·
Tel. +49 (0) 21 04 / 30 32-0
·
Fax +49 (0) 21 04 / 30 32-22
·
www.hengesbach.com
13
Disposal
A certain packaging effort is required to protect the device against damage during transport. Please recycle the packaging materials
correctly or reuse them for packing other items.
The devices consist of a number of different materials, all of which need to be specifically disposed of. Therefore, please dispose of the
devices via a suitable recycling specialist or return them to the manufacturer for the purpose of disposal.
The device is not subject to the WEEE directive 2002/96/EC and its associated laws and regulations. Therefore,
obsolete devices are not designed for disposal in communal recycling centres.
14
Error diagnosis and remedy
If the device does not perform as expected, please check the following points before contacting the manufacturer.
Fault
Possible causes
Check / correction
The device does not start or no current is
flowing in the loop/the status LED remains
out
The voltage of the power supply is
reversed or incorrectly connected.
Make sure that the power supply is
connected correctly.
The power supply is not switched on.
Use a voltmeter to check whether voltage is
applied to the transmitter.
The supply line has a broken cable.
The slide switch is in position C
Return the slide switch to position N
The current value is outside the range of
4...20 mA.
The transmitter has been applied with a
pressure, which is outside the set
measuring range.
Return the transmitter to its set measuring
range.
The transmitter membrane was damaged
Repair of the membrane is not possible -
contact the manufacturer
The current value is constant at 22mA
The device is over-modulated
Return the transmitter to its set measuring
range.
Device fault
Perform a device reset by setting the
factory settings. If the problem persists,
contact the manufacturer